| Date |
Text |
| 2010-02-02 14:39:29 | DENIED* |
| | |
| | |
| | 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS SUBMITTED |
| | AS REQUIRED PER 13-415.AB.5. |
| | PLEASE BE SURE THE FIXTURE LEGEND IS SUBMITTED FOR NEW |
| | FIXTURES AND INFORMATION ON OTHERS. |
| | PLANS HAVE AN *EX* NEXT TO A COUPLE OF FIXTURES HOWEVER |
| | SINCE THE SYMBOL LEGEND DOES NOT INDICATE WHAT THIS IS, |
| | IT IS NOT POSSIBLE TO KNOW EXACTLY WHAT THESE ARE. |
| | EVEN WHEN NOT MEETING THE DEFINITIONS OF A RENOVATION, |
| | PRESCRIPTIVE REQUIREMENTS MUST BE MET. 13-400.B.0.4 |
| | |
| | 2) NOTE: LIGHTING CONTROLS IN SOME AREAS NOT MEETING |
| | FBC 13-415.AB.1.1,.1.2. PLEASE SEE SEPARATE SPACE |
| | REQUIREMENTS. ROOMS ARE NOT IDENTIFIED ON ELECTRICAL |
| | PLANS SO DESIGNATIONS ON ARCHITECTURAL SHEETS ARE BEING |
| | USED. |
| | PLEASE SEE ROOMS 100, 206, 211 ETC |
| | |
| | 3) NOTE: PANEL SCHEDULES AND CIRCUITING TO BE COMPLETE |
| | TO SPECIFIC ROOMS AND AREAS IN WHICH THEY FEED. 408.4. |
| | ( MAY BE ALPHA OR NUMERIC DESIGNATIONS.) |
| | |
| | 4) NOTE: PLEASE COORDINATE RISER DIAGRAM OR PANEL |
| | INFORMATION FOR NEW PANEL FEED SUBMITTED. |
| | RISER INDICATES NEW PANEL AS 60AMP HOWEVER PANEL ON |
| | SHEET E-2 STATES THIS AS A 200AMP MCB PANEL? |
| | 3/0 AWG WILL NOT FIT INTO 60AMP LUGS. |
| | 215.5, 310.16, 240.4 ETC. NO INFORMATION SUBMITTED SO |
| | REVIEW OF NEW PANEL FEED CAN NOT BE DONE. |
| | |
| | 5) NOTE: LOADS ON NEW PANEL ARE ACTUALLY BLANK. THERE |
| | IS NO LOAD INFORMATION FOR THIS PANEL OR ON THE |
| | PANELS/SERVICE EQUIPMENT WHICH FEEDS NEW PANEL. THIS |
| | NEEDS TO BE COMPLETED FOR LOADS ON PANEL K AND A1. |
| | PLEASE SEE 220.12,220.14,220.42, 220.44,220.87 ETC |
| | PLEASE ALSO SEE 215.3,230.42, 422.13 FOR CONTINUOUS |
| | LOADS. |
| | ** SECTIONS GIVEN IN GENERAL AS NO LOADS, LOAD |
| | CALCULATIONS WERE SUBMITTED FOR PANELS BEING AFFECT. |
| | THE LOAD SHOWN FOR SERVICE IS ONLY PART OF THE |
| | INFORMATION NEEDED. |
| | |
| | 6) NOTE: NO INFORMATION SHOWN FOR ADA COMPLIANCE FOR |
| | FBC 11-4.1,.2 AND .3. SHOW LOCATIONS, HEIGHTS AND |
| | LEVELS OF ALL REQUIRED DEVICES. PLEASE COMPLETE LEGEND |
| | FOR MINIMUM REQUIRED DEVICES. |
| | |
| | 7) NOTE: PLEASE SEE FBC 1006.1.2, NFPA-101 |
| | 7.8.1.3,7.9.1.2, .2.2 FOR REQUIRED EMERGENCY EGRESS |
| | LIGHTS. NONE SHOWN ON ELECTRICAL PLANS. PLEASE ALSO SEE |
| | NEC 700.12F FOR CIRCUITING REQUIREMENTS. |
| | A FEW ARE LOCATED ON E-1 HOWEVER NOT ALL REQUIRED. |
| | |
| | 8) NOTE: PLEASE COMPLETED PLANS FOR LIGHTING AND FAN |
| | CONTROLS IN BATHROOM AREAS. SEE NOTES ABOVE WITH |
| | RESPECT TO FBC CHAPTER 13 FOR LIGHTING CONTROLS AND |
| | ALSO MINIMUM REQUIRED FOR NORMAL AND EMERGENCY EGRESS. |
| | |
| | 9) NOTE: PER PANEL SCHEDULE ONE OF THE ROOMS WILL BE A |
| | NEW SERVER ROOM. IF THIS IS *NOT* AN IT ROOM PER 645.4 |
| | (1-5) THEN PLEASE PLACE NOTE ON PLANS WHICH WILL *NOT* |
| | PERMIT THE WIRING METHODS PERMITTED IN NEC 645. THE |
| | WORDING TO THAT AFFECT MAY BE ADJUSTED. |
| | |
| | ** FYI: IT PERSONNEL FOR OWNER MAY WANT TO BE CONSULTED |
| | WITH DUE THE MORE STRINGENT WIRING METHODS REQUIRED |
| | WHEN NOT AN IT ROOM. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |