| Plan Review Notes For Permit 10010378 |
| Permit Number |
10010378 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2010-03-31 16:27:45 | ****PROVISO**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. DESIGN PRESSURES ARE TOO LOW. SEE FBC R TABLE | | | 301.2(2) AND FBC R TABLE 301.2(3). BASED ON OPENING | | | SIZE, IF OPENING 8 IS IN ZONE 5, 15' BUILDING HEIGHT, | | | BETWEEN 20 AND 50SF, -53.24 MINIMUM DESIGN PRESSURE | | | REQUIRED. PLEASE PROVIDE BUILDING HEIGHT SO MINIMUM | | | DESIGN PRESSURE REQUIREMENTS CAN BE DETERMINED. PLEASE | | | CONTACT ME IF YOU NEED ASSISTANCE. | | | | | | PROVIDE REVISED INSTALLATION SCHEDULE FOR EXPOSURE C AT | | | INSPECTION | | | |
|