Plan Review Notes
Plan Review Notes For Permit 10010321
Permit Number 10010321
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-03 15:12:36*DENIED*
  
  
 1) NOTE: SHEET 8 OF 10 CONTAINS CODES REFERENCES WHICH
 ARE NO LONGER ADOPTED WITH THE STATE OF FLORIDA. THE
 FLORIDA FIRE PREVENTION CODE AND LIFE SAFETY CODES WERE
 CHANGED DECEMBER 31ST, 2008. THE FLORIDA BUILDING CODES
 FOR FUEL GAS AND PLUMBING AS NOTED WERE REVISED ON
 MARCH 1ST 2009 AND THE NFPA-70 WAS REVISED OCTOBER 1ST,
 2009.
 PLEASE BE SURE TO ADJUST ALL OF THE FOLLOWING RELEVANT
 CODES AS APPLICABLE TO PROJECT.
  
 2008 NFPA-70
 2005 NFPA-110
 2006 NFPA -101
 2007 FLORIDA FIRE PREVENTION CODE
 2007 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENTS.
  
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWERS.
  
 2) NOTE: ENGINEERING FIRM MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER ON TITLE BLOCKS. PLANS CONTAIN A
 NOTE THAT THE NUMBER IS TO BE PROVIDED HOWEVER
 LICENSURE IN THE STATE OF FLORIDA IS REQUIRED AT THIS
 TIME.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 FLORIDA STATUTES 471.023.
 ** THIS IS REQUIRED ON ALL PLANS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE.
 ** AS IT MAY TAKE SOME TIME FOR CERTIFICATE OF
 AUTHORIZATION NUMBER THERE ARE OPTIONS HOWEVER PLEASE
 CALL TO GO OVER.
  
 3) NOTE: PLEASE SUBMIT TWO COPIES OF THE MANUFACTURES
 SPECS/CUT SHEETS FOR GENERATOR, ATS AND FUEL TANK.
 ONE SET SUBMITTED ONLY. SEE COMMENTS FROM OTHER TRADES
 FOR REVIEW STAMPS ETC.
 90.7,110.3,701.6, 701.7.
  
 4) NOTE: COLOR CODING FOR CONDUCTORS SHALL BE BROWN,
 PURPLE, YELLOW FOR 277/480V SYSTEMS. SPECIFICATION
 SHEETS INDICATE ORANGE FOR B HASE AS THIS IS NOT AN
 OPEN DELTA HIGH-LEG SYSTEM PLEASE ADJUST COLOR CODING.
 90.4.
 EXISTING SYSTEM WIRING WITHIN THIS MUNICIPALITY AND
 COUNTY ARE BASED ON PREVIOUS TECHNICAL AMENDMENTS. IN
 KEEPING WITH THE SAFETY ASPECT OF IDENTIFICATION OF
 SUCH SYSTEMS THIS JURISDICTION WILL REQUIRE THE ABOVE.
  
 5) NOTE: PLANS MENTION ON SHEET 3 OF 10 TO REMOVE
 CONCRETE, GRIND ETC. THIS WILL CREATE CONTAMINATES
 WITHIN THE ELECTRICAL EQUIPMENT ENCLOSURES. PLEASE BE
 SURE TO NOTE THAT ALL EQUIPMENT SHALL BE COVERED OR
 PROTECTED.
 PLEASE KNOW THAT DUST, DETERIORATING AGENTS AND
 MOISTURE MITIGATION NEEDS TO BE ADDRESSED.
  
 6) NOTE: PLEASE SEE 225.31-225.39. A DISCONNECTING
 MEANS IS REQUIRED FOR FEEDERS COMING INTO BUILDING
 UNLESS MEETING THE EXCEPTIONS IN 701.11B5. THE
 DISCONNECTING MEANS AT THE GENERATOR MAY BE USED WHEN
 MEETING BOTH WITHIN SIGHT ( 50FT) AND READILY
 ACCESSIBLE. THE GENERATOR IS WITHIN SIGHT HOWEVER THE
 GENERATOR DISCONNECTING MEANS IS NOT READILY
 ACCESSIBLE.
 PLEASE KNOW THAT THE *MUSHROOM* TYPE PUSH/PULL BUTTON
 AT THE BUILDING DOES NOT MEET SECTIONS ABOVE AS THE
 DISCONNECTING MEANS IS REQUIRED TO BE RATED FOR THE
 LOAD SERVED.225.39.
 THE DISCONNECT AT THE BUILDING DOES NOT REQUIRE OVER
 CURRENT PROTECTION IF THE OVER CURRENT PROTECTION IS
 PROVIDED AT THE GENERATOR. IT ONLY REQUIRES THIS TO BE
 A DISCONNECT.
  
 7) NOTE: ALL PULL BOX DIMENSIONS WILL BE REQUIRED TO BE
 LOCATED ON PLANS SIZED IN ACCORDANCE WITH MINIMUM NEC
 REQUIREMENTS.
 PLEASE SEE CHANGES IN 2008 NEC. 314.28
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  