| 2010-02-03 15:12:36 | *DENIED* |
| | |
| | |
| | 1) NOTE: SHEET 8 OF 10 CONTAINS CODES REFERENCES WHICH |
| | ARE NO LONGER ADOPTED WITH THE STATE OF FLORIDA. THE |
| | FLORIDA FIRE PREVENTION CODE AND LIFE SAFETY CODES WERE |
| | CHANGED DECEMBER 31ST, 2008. THE FLORIDA BUILDING CODES |
| | FOR FUEL GAS AND PLUMBING AS NOTED WERE REVISED ON |
| | MARCH 1ST 2009 AND THE NFPA-70 WAS REVISED OCTOBER 1ST, |
| | 2009. |
| | PLEASE BE SURE TO ADJUST ALL OF THE FOLLOWING RELEVANT |
| | CODES AS APPLICABLE TO PROJECT. |
| | |
| | 2008 NFPA-70 |
| | 2005 NFPA-110 |
| | 2006 NFPA -101 |
| | 2007 FLORIDA FIRE PREVENTION CODE |
| | 2007 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENTS. |
| | |
| | ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWERS. |
| | |
| | 2) NOTE: ENGINEERING FIRM MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON TITLE BLOCKS. PLANS CONTAIN A |
| | NOTE THAT THE NUMBER IS TO BE PROVIDED HOWEVER |
| | LICENSURE IN THE STATE OF FLORIDA IS REQUIRED AT THIS |
| | TIME. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, |
| | FLORIDA STATUTES 471.023. |
| | ** THIS IS REQUIRED ON ALL PLANS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE. |
| | ** AS IT MAY TAKE SOME TIME FOR CERTIFICATE OF |
| | AUTHORIZATION NUMBER THERE ARE OPTIONS HOWEVER PLEASE |
| | CALL TO GO OVER. |
| | |
| | 3) NOTE: PLEASE SUBMIT TWO COPIES OF THE MANUFACTURES |
| | SPECS/CUT SHEETS FOR GENERATOR, ATS AND FUEL TANK. |
| | ONE SET SUBMITTED ONLY. SEE COMMENTS FROM OTHER TRADES |
| | FOR REVIEW STAMPS ETC. |
| | 90.7,110.3,701.6, 701.7. |
| | |
| | 4) NOTE: COLOR CODING FOR CONDUCTORS SHALL BE BROWN, |
| | PURPLE, YELLOW FOR 277/480V SYSTEMS. SPECIFICATION |
| | SHEETS INDICATE ORANGE FOR B HASE AS THIS IS NOT AN |
| | OPEN DELTA HIGH-LEG SYSTEM PLEASE ADJUST COLOR CODING. |
| | 90.4. |
| | EXISTING SYSTEM WIRING WITHIN THIS MUNICIPALITY AND |
| | COUNTY ARE BASED ON PREVIOUS TECHNICAL AMENDMENTS. IN |
| | KEEPING WITH THE SAFETY ASPECT OF IDENTIFICATION OF |
| | SUCH SYSTEMS THIS JURISDICTION WILL REQUIRE THE ABOVE. |
| | |
| | 5) NOTE: PLANS MENTION ON SHEET 3 OF 10 TO REMOVE |
| | CONCRETE, GRIND ETC. THIS WILL CREATE CONTAMINATES |
| | WITHIN THE ELECTRICAL EQUIPMENT ENCLOSURES. PLEASE BE |
| | SURE TO NOTE THAT ALL EQUIPMENT SHALL BE COVERED OR |
| | PROTECTED. |
| | PLEASE KNOW THAT DUST, DETERIORATING AGENTS AND |
| | MOISTURE MITIGATION NEEDS TO BE ADDRESSED. |
| | |
| | 6) NOTE: PLEASE SEE 225.31-225.39. A DISCONNECTING |
| | MEANS IS REQUIRED FOR FEEDERS COMING INTO BUILDING |
| | UNLESS MEETING THE EXCEPTIONS IN 701.11B5. THE |
| | DISCONNECTING MEANS AT THE GENERATOR MAY BE USED WHEN |
| | MEETING BOTH WITHIN SIGHT ( 50FT) AND READILY |
| | ACCESSIBLE. THE GENERATOR IS WITHIN SIGHT HOWEVER THE |
| | GENERATOR DISCONNECTING MEANS IS NOT READILY |
| | ACCESSIBLE. |
| | PLEASE KNOW THAT THE *MUSHROOM* TYPE PUSH/PULL BUTTON |
| | AT THE BUILDING DOES NOT MEET SECTIONS ABOVE AS THE |
| | DISCONNECTING MEANS IS REQUIRED TO BE RATED FOR THE |
| | LOAD SERVED.225.39. |
| | THE DISCONNECT AT THE BUILDING DOES NOT REQUIRE OVER |
| | CURRENT PROTECTION IF THE OVER CURRENT PROTECTION IS |
| | PROVIDED AT THE GENERATOR. IT ONLY REQUIRES THIS TO BE |
| | A DISCONNECT. |
| | |
| | 7) NOTE: ALL PULL BOX DIMENSIONS WILL BE REQUIRED TO BE |
| | LOCATED ON PLANS SIZED IN ACCORDANCE WITH MINIMUM NEC |
| | REQUIREMENTS. |
| | PLEASE SEE CHANGES IN 2008 NEC. 314.28 |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |