| Plan Review Notes For Permit 10010307 |
| Permit Number |
10010307 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-26 09:34:52 | ****REVISION REQUIRED**** | | | ****ISSUED WITH PROVISO**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. REVISE EXPOSURE CATEGORY (TO EXPOSURE C) OR EXPLAIN | | | RATIONALE FOR EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE | | | THAT THE CODE CHANGED EFFECTIVE MARCH 1, 2009. | | | | | | 2. PLEASE PROVIDE LEGIBLE PRODUCT APPROVALS. THE SETS | | | PROVIDED ARE COPIES OF A FAX, ARE DIFFICULT TO READ, | | | AND WILL FURTHER LOSE LEGIBILITY WHEN SCANNED FOR | | | RECORD KEEPING. LEGIBLE COPIES SHOULD BE AVAILABLE AT | | | WWW.MIAMIDADE.GOV. | | | | | | 3. WALL SECTION CONFLICTS WITH NOTE. A BOND BREAK IS | | | REQUIRED FOR STUCCO, R703.7.3 (WALL LEGEND ON A2 | | | COMPLIES, WALL SECTION A DOES NOT COMPLY. | | | | | | 4. PRIOR TO ISSUANCE, PROVIDE A CONTRACT FOR THIS JOB. | | | | | | |
|