| 2010-02-01 15:11:10 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. VENTILATION CALCULATIONS CALL FOR AIR EXHCHANGES PER | | | HOUR. PLAN SHOWS EXHAUST FAN HANGING DETAIL BUT NO | | | EXHAUST FAN LOCATIONS ARE SHOWN ON PLANS. ALSO, EXHAUST | | | FANS ARE NOT SHOWN ON THE ELECTRICAL PLANS. SHOW ON | | | PLANS HOW THE REQUIRED AIR EXCHANGES ARE TO BE ACHIEVED | | | WITHOUT ANY EXHAUST OR SHOW THE EXHAUST ON THE PLANS, | | | INCLUDING EXHAUST DISCHARGE LOCATION. | | | | | | 2. THE PRINTED NAME AND LICENSE NUMBER OF THE ENGINEER | | | SHALL APPEAR ON THE PLANS IN ACCORDANCE WITH FAC | | | 61G15-23.002. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|