| 2010-02-01 16:35:38 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. PLANS PREPARED BY A LICENSED DESIGN PROFESSIONAL, |
| | (LANDSCAPE ARCHITECT), SHALL BE SIGNED, SEALED AND |
| | DATED BY THE DESIGN PROFESSIONAL. SECTION 106.1, FAC |
| | 61G1.10 & FS 481.321. PLANS SUBMITTED ARE COPIES OF |
| | SIGNED/SEALED/DATED PLANS. |
| | |
| | 2. SHT 2 0F 2 SHOW THE LOCATION OF THE METER, THE |
| | BACKFLOW, THE CONTROLLER AND THE RAIN SENSOR ON THE |
| | PLANS. SECTION 106.1.1. |
| | |
| | 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED. SECTION |
| | 105.1. |
| | |
| | 4. A SEPARATE BACKFLOW PERMIT IS REQUIRED. BACKFLOW |
| | SHALL BE INSTALLED BY A LICENSED PLUMBING CONTRACTOR. |
| | FS 489.105(M) & SECTION 608.13.2/608.13.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |