| Plan Review Notes For Permit 10010259 |
| Permit Number |
10010259 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-02-01 15:34:42 | | | | ** DENIED REVIEW * | | | | | | 1) NOTE: NO DESIGN CODES ON PLANS FOR PERMIT | | | APPLICATION MADE AFTER OCTOBER 1ST, 2009. | | | SHOULD HAVE THE FOLLOWING AT A MINIMUM. | | | 2008 NFPA-70 | | | 2006 NFPA-101 | | | | | | 2) NOTE: MIXED USE OCCUPANCY CLASSIFICATION UNDER FBC | | | CHAPTER 3. THIS IS A COMMERCIAL OFFICE SPACE. | | | PLEASE SEE FBC CHAPTER 13, 13-415.AB.5 FOR LIGHTING | | | PERFORMANCE CALCULATIONS. THE SUBMITTED FORM FOR | | | RESIDENTIAL USE IS NOT ACCEPTABLE. THE PERSON PREPARING | | | DOCUMENTS MUST HAVE AN ORIGINAL SIGNATURE. THE | | | SUBMITTED FORM IS NOT ORIGINAL SIGNATURE. | | | FBC 13-103.1 | | | | | | 3) NOTE: PLEASE SUBMIT PANEL SCHEDULE AND LOAD | | | CALCULATIONS FOR OCCUPANCY AND ADJUST PER NEC | | | 220.12,220.14,220.42 ETC | | | PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%. | | | 215.3, 230.42 | | | | | | 4) NOTE: PLEASE SEE NEC AND FBC FOR *TEMPORARY USE* AND | | | TIME LIMITATIONS. | | | RE-PLAT HOLD STILL ON SYSTEM TO BE ADDRESSED BEFORE USE | | | PROPOSED. NEEDS TO BE A FEE SIMPLE TOWN-HOUSE. THIS IS | | | NOT A MULTI-FAMILY BUILDING OR CONDO. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|