Plan Review Notes
Plan Review Notes For Permit 10010253
Permit Number 10010253
Review Stop P
Sequence Number 2
Notes
Date Text
2010-03-02 13:16:28DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT SHT D1 DEMO NOTE #11 INDICATES THE REMOVAL OF A
 DRINKING FOUNTAIN. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. IF THERE ARE OTHER DRINKING FOUNTAINS IN
 THE TENANT SPACE PLEASE INDICATE THE LOCATION.
 ****RESPONSE NOTED, BUT THE REQUIRED DRINKING FOUNTAIN
 IS NOT INDICATED. A SINK IS NOT AN ACCEPTABLE
 REPLACEMENT FOR THE REQUIRED DRINKING FOUNTAIN.
  
 2. THE SINK SHALL COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE SUBMIT A DETAIL FOR THE FOLLOWING:
 A. OK
 B. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. (SEE FIG 32).
 ****NOT SHOWN ON FLOOR PLAN. -- CABINET DOORS ARE
 PROHIBITED IN THE "CLEAR FLOOR SPACE" PLEASE DELETE
 FROM ELEVATION.
 C. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  