| Plan Review Notes For Permit 10010253 |
| Permit Number |
10010253 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-27 14:08:42 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | FBC-2007 CHAPTER 11 | | | | | | 1. SHT SHT D1 DEMO NOTE #11 INDICATES THE REMOVAL OF A | | | DRINKING FOUNTAIN. PER TABLE 403.1 A DRINKING FOUNTAIN | | | IS REQUIRED. IF THERE ARE OTHER DRINKING FOUNTAINS IN | | | THE TENANT SPACE PLEASE INDICATE THE LOCATION. | | | | | | 2. THE SINK SHALL COMPLY WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS. PLEASE SUBMIT A DETAIL FOR THE FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH | | | REQUIRED MAX 19" UNDERNEATH THE SINK. (SEE FIG 32). | | | C. 11-4.24.6 EXPOSED PIPES & SURFACES | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|