Plan Review Notes
Plan Review Notes For Permit 10010253
Permit Number 10010253
Review Stop P
Sequence Number 1
Notes
Date Text
2010-01-27 14:08:42DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 1. SHT SHT D1 DEMO NOTE #11 INDICATES THE REMOVAL OF A
 DRINKING FOUNTAIN. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. IF THERE ARE OTHER DRINKING FOUNTAINS IN
 THE TENANT SPACE PLEASE INDICATE THE LOCATION.
  
 2. THE SINK SHALL COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE SUBMIT A DETAIL FOR THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. (SEE FIG 32).
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  