2010-01-28 16:17:26*****DENIED*****
  
  
 1. ON SHEET T1 IN THE APPLICABLE BUILDING CODES,
 REFERENCE IS INCORRECTLY MADE TO PALM BEACH COUNTY
 AMENDMENTS. REFERENCE AS PER THE CITY OF WEST PALM
 BEACH.
  
 2. ON SHEET T1, IT IS INDICATED THAT THE BUILDING IS
 PARTIALLY SPRINKLERED. VERIFY AND/OR EXPLAIN THIS
 ARRANGEMENT.
  
 3. PLEASE SHOW THE LOCATION OF EXIT LIGHTS AND
 EMERGENCY LIGHTS FOR THE PROPOSED FLOOR PLAN.
  
  