2010-02-24 10:26:08****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ***REVISION REQUIRED PRIOR TO FIRST INSPECTION***
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR
 EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE
 CHANGED EFFECTIVE MARCH 1, 2009.
  
 EXPOSURE B PLANS SUBMITTED. PLEASE SEE FBC R301.2.1.4.
 ALSO SEE THE ENGINEERING SUBMITTED, SHEET 3: EXPOSURE C
 INCLUDES A SITE WHICH HAS OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS EXTENDING MORE THAN 1500 FEET FROM THE
 BUILDING SITE IN ANY QUADRANT. THIS PARCEL IS LOCATED
 ONE LOT FROM A PRESERVE; THEREFORE IT APPEARS THAT THIS
 WOULD BE CONSIDERED EXPOSURE C. IF THE ENGINEER WOULD
 LIKE TO PROVIDE A JUSTIFICATION FOR HIS RATIONALE FOR
 EXPOSURE B, PLEASE SUBMIT AS REQUESTED. A STATEMENT WAS
 HANDWRITTEN ON A COPY OF THE CODE (NOT INCLUDED IN THE
 ENGINEERING) WHICH STATES THAT THIS PARCEL IS 230 FEET
 FROM THE WATER, BUT THIS DOES NOT ADDRESS THE COMMENT -
 THE CODE REFERENCED CIRCLED IS RELATED TO THE
 REQUIREMENT FOR INCREASED ROOF UPLIFT DESIGN LOADS. THE
 CODE CIRCLED STATES THAT "EXPOSURE C SHALL APPLY FOR
 ALL CASES WHERE EXPOSURE B DOES NOT APPLY"; PLEASE SHOW
 HOW EXPOSURE B APPLIES TO THIS JOB BASED ON THE
 DEFINITION. THE RATIONALE FOR EXPOSURE B IS TO BE
 PREPARED BY THE ENGINEER.
  
 THE AAF WEBSITE HAS POSTED A DRAFT COMMENTARY ON THIS
 ISSUE WHICH YOU MAY FIND HELPFUL.
  
 THIS PERMIT IS ISSUED WITH PROVISO THAT EITHER NEW
 ENGINEERING BE SUBMITTED WITH EXPOSURE C CRITERIA OR
 RATIONALE FOR EXPOSURE B BE PROVIDED BY ENGINEER OF
 RECORD WHO IS TAKING RESPONSIBILITY FOR THE DESIGN.
 CONTRACTOR ASSUMES FULL RISK FOR WORK PERFORMED PRIOR
 TO ACCEPTANCE OF EXPOSURE B CRITERIA.
  
 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471.
  
 DOCUMENTS SUBMITTED ARE SEALED BUT INCLUDE A PHOTOCOPY
 SIGNATURE. PLEASE PROVIDE DOCUMENTS IN COMPLIANCE WITH
 THE FLORIDA STATUTE OR ADVISE AS TO ANY CHANGES IN FBPE
 POLICY.
  
  
 PLANS HAVE BEEN RETAINED BUT NOT ISSUED AS A PART OF
 THIS PERMIT. ENGINEERED PLANS REQUIRED PRIOR TO FIRST
 INSPECTION.
  
  
  