| 2010-01-27 11:23:42 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR |
| | EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE |
| | CHANGED EFFECTIVE MARCH 1, 2009. |
| | |
| | 2. THE MARKINGS ON THE DOCUMENTS SUBMITTED HAVE MADE |
| | SOME OF THE TEXT ILLEGIBLE (HIGHLIGHTER OVER PHOTOCOPY |
| | INK WHICH SMEARED). PLEASE PROVIDE ENTIRELY LEGIBLE |
| | DOCUMENTS WHICH WILL REMAIN LEGIBLE AFTER SCANNING. |
| | NOTE THAT HIGHLIGHTER DOES NOT APPEAR, SO WHILE IT MAY |
| | BE HELPFUL TO ADD HIGHLIGHTER TO ASSIST IN INSPECTIONS |
| | AND REVIEW, INK SHOULD BE USED TO PERMANENTLY NOTE |
| | DETAILS WHICH DEMONSTRATE CODE COMPLIANCE FOR THIS |
| | PROJECT. |
| | |
| | 3. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS, FS471. |
| | |
| | 4. THE AAF GUIDE HAS BEEN INCORPORATED INTO THE FLORIDA |
| | BUILDING CODE PER FBC R301.2.1.1.1; THE DOCUMENT WHICH |
| | WAS USED TO CREATE THIS PERMIT PACKAGE IS NOT REFERRED |
| | TO IN THE FBC. IF YOU DISAGREE, PLEASE ADVISE AS TO |
| | CODE SECTION. SEE FBC R301.2.1.1, DESIGN CRITERIA, FOR |
| | ACCEPTABLE DESIGN METHODS. IF A PRESCRIPTIVE METHOD |
| | LISTED IS NOT USED FOR DESIGN, AND PLANS ARE NOT SIGNED |
| | AND SEALED, DESIGN PROPOSED IS TO BE SUPPORTED WITH |
| | CALCULATIONS FOR ALL STRUCTURAL MEMBERS AND |
| | ATTACHMENTS. |
| | |