Plan Review Notes
Plan Review Notes For Permit 10010227
Permit Number 10010227
Review Stop P
Sequence Number 2
Notes
Date Text
2010-02-02 15:12:33DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
 FBC-2007 CHAPTER 1
  
 1. SHT P.1 2ND FLOOR SANITARY ISOMETRIC RISER DIAGRM
 DOES NOT REFLECT THE CHANGES SHOWN ON SECOND FLOOR
 PLUMBING PLAN. ALL CHANGES TO THE FLOOR PLAN SHALL BE
 INDICATED ON THE RISER DIAGRAM. SECTION 106.1.1
  
 2. SHT P.1 FIRST FLOOR PLUMBING PLAN & 1ST FLOOR
 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENT. THE WATER CLOSET IN THE BATHROOM IS NOT
 VENTED AS SHOWN. THE 2ND FLOOR BATHROOM FIXTURES, THE
 KITCHEN SINK, THE LAUNDRY TUB & THE WASH MACHINE DRAIN
 PAST THE WATER CLOSET THAT IS NOT VENTED. SECTIONS
 P3101.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  