2010-01-14 11:24:482007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO COPIES OF THE SIMPLIFIED TDH CALCULATIONS
 USED TO DETERMINE THE TDH FOR THE POOL AND SPA THAT IS
 SPECIFIED ON THE PLANS. FBC R 4101.6.1
  
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND DATA SHEETS WHICH INCLUDE THE PUMP
 CURVE CHART FOR THE POOL PUMP THAT WILL BE INSTALLED.
 FBC R 4101.6.3 AND R4101.7.2
  