| Plan Review Notes For Permit 10010195 |
| Permit Number |
10010195 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-12 16:42:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. PROVIDE REVISE PLAN TO SHOWING ROOM DESIGNATIONS AND | | | WINDOW LOCATIONS (SEE COMMENT 2). NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | IF THIS WINDOW SERVES AS THE EMERGENCY EGRESS FOR A | | | BEDROOM ON THE SECOND FLOOR, AND A 25X36 WINDOW IS | | | INSTALLED, THE CLEAR OPENING WILL HAVE A HEIGHT OF LESS | | | THAN 15". | | | | | | 2. SCOPE OF WORK NOT CLEAR. THE APPLICATION STATES "2" | | | BUT THE PLAN SHOWS ONE WINDOW TO BE REPLACED. PLEASE | | | REVISE. |
|