| Date |
Text |
| 2010-01-20 17:01:09 | ** DENIED * |
| | |
| | 1) NOTE: PLANS STATE 2004 FLORIDA BUILDING CODE WITH |
| | 2006 AND 2007 AMENDMENTS. |
| | ALL PERMIT APPLICATIONS MADE AFTER MARCH 1ST, 2009 AND |
| | OCTOBER 1ST, 2009 HAVE NEW CODES. |
| | |
| | PLANS SHOULD HAVE THE FOLLOWING. |
| | 2007 FBC W/ 2009 SUPPLEMENTS |
| | 2008 NFPA-70 ( NEC). |
| | |
| | 2) NOTE: ALL HORN, STROBE AND DEVICE LEVELS AND HEIGHTS |
| | TO BE PART OF SYMBOL LEGEND FOR ADA COMPLIANCE. FBC |
| | 11-4.28, .1, .2 AND .3. |
| | BASE PLANS ARE REQUIRED TO SHOW BASE DESIGN INTENT EVEN |
| | THOUGH FIRE ALARM WILL BE UNDER SEPARATE PERMITS. |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-415.AB.5 FOR INTERIOR |
| | LIGHTING PERFORMANCE CALCULATIONS. THE * J* FIXTURES |
| | WHICH ARE SHOWN ON LEGEND AND IN CALCULATIONS FOR |
| | RESTROOM COULD NOT BE LOCATED ON PLANS. |
| | THE B1 FIXTURE ON THE CALCULATIONS IS SHOWN AS 20W |
| | FIXTURE HOWEVER BASED ON THE FIXTURE LISTED THIS IS A |
| | 70W FIXTURE. THE RATING OF THE FIXTURE NOT THE BULB IS |
| | REQUIRED TO BE USED FOR PERFORMANCE CALCULATIONS. |
| | |
| | 4) NOTE: ALL CIRCUITING IS REQUIRED TO BE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. SOME CIRCUITS FOR |
| | EXAMPLE A-29 APPEARS TO BE DEDICATED FOR A REFRIGERATOR |
| | HOWEVER PANEL SCHEDULE ONLY INDICATES THIS AS AN |
| | *EXISTING RECEPT*. |
| | LOADS FOR ALL CIRCUITS AND PANEL CAN NOT BE VERIFIED |
| | WITHOUT THIS SPECIFIC INFORMATION. DESIGNATION FOR |
| | AREAS AND ROOMS MAY BE ALPHA OR NUMERIC. |
| | PLEASE SEE 408.4 SPECIFIC, SEE COMMENTARY IN HANDBOOK, |
| | 220, 310.16 GIVEN IN GENERAL FOR LOADS AND SIZING OF |
| | BRANCH CIRCUITS. |
| | ** ONCE COMMENTS 1-3 ABOVE ARE ADDRESSED THIS COMMENT |
| | MAY BE SET UP AS A PROVISO TO HAVE ALL CIRCUITING CAN |
| | BE UPDATED AND ACCURATE IN THE PANEL SCHEDULE BEFORE |
| | FINAL. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |