| Plan Review Notes For Permit 10010151 |
| Permit Number |
10010151 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-02-16 13:21:52 | *****DENIED***** | | | | | | | | | 1. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING THE SUITE | | | NUMBER, SHALL BE INCLUDED IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 3. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW | | | WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR | | | CLASS C. | | | | | | 5. SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS, | | | FIRE EXTINGUISHER(S), AND ANY OTHER LIFE SAFETY DEVICES | | | ON THE FLOOR PLAN OF THIS PROJECT SITE. | | | | | | 6. SHOW THE LAYOUT OF THE RECONFIGURED FIRE ALARM | | | DEVICES AND/OR FIRE SPRINKLER HEADS FOR THE NEW FLOOR | | | LAYOUT. BE ADVISED THAT SEPARATE PLANS AND PERMIT WILL | | | BE REQUIRED FOR THE REMODELING OF THIS/THESE SYSTEMS. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|