| Plan Review Notes For Permit 10010099 |
| Permit Number |
10010099 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-07 14:29:52 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- FLAT ROOF COMMENTS: | | | A) SELECTED FLAT ROOF APPROVED SYSTEM W-26 ON SHEET 10 | | | OF 32 IS GOOD FOR THE DESIGN PRESSURES OF -60PSF. NEED | | | TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY LIMITATION #5.6 ON SHEET 4 OF 5 TO MEET THE | | | DESIGN PRESSURES AT ROOF PERIMETER AND CORNER AREAS. | | | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS | | | BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". SEC. | | | R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 RESIDENTIAL | | | CODE. | | | | | | 2- ACCORDING TO MIAMI-DADE COUNTY WEBSITE NOA | | | 07-0111.03 SUBMITTED IS SUPERSEDED. NEED TO PROVIDE | | | CURRENT NOA. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|