| Plan Review Notes For Permit 10010097 |
| Permit Number |
10010097 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-03-09 14:14:05 | OFFICE BUILDING ALTERATION, BUILDING REVIEW SECOND | | | CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- REVISED DOORS ARE OBSTRUCTING THE CORRIDOR LEADING | | | TO THE STAIRWAY #2. THESE DOORS DON'T COMPLY WITH SEC. | | | 1008.1.8.8 FBC 2007. REVISE AS REQUIRED. | | | | | | 2- OWES $238.05 FOR UPDATED VALUATION. | | | | | | 3- REVISE ALL OTHER DRAWINGS TO MATCH REVISED DRAWING | | | SHEET A-3. NEED TO REVISE THE LIFE SAFETY FLOOR PLAN | | | AND ANY OTHER FLOOR PLAN THAT NEEDS TO BE REVISED TO | | | MATCH SHEET A-3. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|