| 2010-01-26 10:24:39 | OFFICE BUILDING ALTERATION, BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- NEW DOORS NEED TO SWING ON THE DIRECTION OF EGRESS | | | TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR MORE | | | PERSONS (97 PEOPLE. SEE SHEET T). SEC. 1001.4 AND SEC. | | | 1008.1.2 OF FBC 2007 WHEN | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. UPDATE PERMIT VALUATION TO INCLUDE ALL DEMOLITION, | | | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN | | | PROFESSIONAL FEES AS REQUIRED BY SEC. 108.3 OF CITY | | | AMENDMENTS TO FBC. | | | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | COMBINATION COMMERCIAL PLANS EXAMINER | | | (561)805-6712 | | | |
|