Plan Review Notes
Plan Review Notes For Permit 10010084
Permit Number 10010084
Review Stop B
Sequence Number 2
Notes
Date Text
2010-02-10 11:17:17BUILDING P 10010084
 ADD: 854 CONNISTON RD
 CONT: CATOE CONSTRUCTION
 TEL: (561)719-6395
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 FEB.10/ 2010
  
 BUILDING APPROVED WITH EXCEPTION!
 SECTION 1034-DAY CARE
 CLASS ROOMS 1,4,7 & 9 DO NOT HAVE DOOR WAYS THAT LEAD
 DIRECTLY TO THE EXTERIOR, REQUIRING THE LARGER 5.7 SQ
 FT (VENT) WINDOW OPENING.
  
 1034.6 SPECIAL MEANS OF EGRESS FEATURES. EVERY ROOM OR
 SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN
 BATHROOMS, SHALL HAVE AT LEAST ONE OUTSIDE WINDOW FOR
 EMERGENCY RESCUE AND VENTILATION. SUCH WINDOW SHALL BE
 OPEN ABLE FROM THE INSIDE WITHOUT THE USE OF TOOLS AND
 SHALL PROVIDE A CLEAR OPENING OF NOT LESS THAN 20
 INCHES (508 MM) IN WIDTH, 24 INCHES (610 MM) IN HEIGHT,
 AND 5.7 SQUARE FEET (0.53 M2) IN AREA (OPEN VENT). THE
 BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 INCHES
 (1118 MM) ABOVE THE FLOOR. THE CLEAR OPENING SHALL
 PERMIT A RECTANGULAR SOLID, WITH A MINIMUM WIDTH AND
 HEIGHT THAT PROVIDES THE REQUIRED 5.7 SQUARE FOOT (0.53
 M2) OPENING AND A MINIMUM DEPTH OF 20 INCHES (8 MM), TO
 PASS FULLY THROUGH THE OPENING.
  
 EXCEPTIONS:
  
 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 AUTOMATIC SPRINKLER SYSTEM.
  
 2. WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY
 TO THE OUTSIDE OF THE BUILDING.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  