| Date |
Text |
| 2010-02-10 11:17:17 | BUILDING P 10010084 |
| | ADD: 854 CONNISTON RD |
| | CONT: CATOE CONSTRUCTION |
| | TEL: (561)719-6395 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | |
| | FEB.10/ 2010 |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | SECTION 1034-DAY CARE |
| | CLASS ROOMS 1,4,7 & 9 DO NOT HAVE DOOR WAYS THAT LEAD |
| | DIRECTLY TO THE EXTERIOR, REQUIRING THE LARGER 5.7 SQ |
| | FT (VENT) WINDOW OPENING. |
| | |
| | 1034.6 SPECIAL MEANS OF EGRESS FEATURES. EVERY ROOM OR |
| | SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN |
| | BATHROOMS, SHALL HAVE AT LEAST ONE OUTSIDE WINDOW FOR |
| | EMERGENCY RESCUE AND VENTILATION. SUCH WINDOW SHALL BE |
| | OPEN ABLE FROM THE INSIDE WITHOUT THE USE OF TOOLS AND |
| | SHALL PROVIDE A CLEAR OPENING OF NOT LESS THAN 20 |
| | INCHES (508 MM) IN WIDTH, 24 INCHES (610 MM) IN HEIGHT, |
| | AND 5.7 SQUARE FEET (0.53 M2) IN AREA (OPEN VENT). THE |
| | BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 INCHES |
| | (1118 MM) ABOVE THE FLOOR. THE CLEAR OPENING SHALL |
| | PERMIT A RECTANGULAR SOLID, WITH A MINIMUM WIDTH AND |
| | HEIGHT THAT PROVIDES THE REQUIRED 5.7 SQUARE FOOT (0.53 |
| | M2) OPENING AND A MINIMUM DEPTH OF 20 INCHES (8 MM), TO |
| | PASS FULLY THROUGH THE OPENING. |
| | |
| | EXCEPTIONS: |
| | |
| | 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 2. WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| | TO THE OUTSIDE OF THE BUILDING. |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |