Plan Review Notes
Plan Review Notes For Permit 10010084
Permit Number 10010084
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-01-28 01:14:46*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 INFORMATIONAL: HAVING KNOWLEDGE OF THE BUILDING THROUGH
 PREVIOUS FIRE INSPECTIONS, BE ADVISED THAT THIS IS A
 CHANGE OF OCCUPANCY FROM AN "EXISTING ASSEMBLY
 OCCUPANCY " TO A "NEW DAY CARE OCCUPANCY". A
 COMPREHENSIVE PLAN REVIEW INCLUDING OTHER DISCIPLINES
 (I.E. BUILDING, ELECTRICAL, PLUMBING, MECHANICAL, ETC)
 SHALL BE REQUIRED FOR THE CHANGE OF OCCUPANCY.
  
 3. PLEASE DETAIL, AS PER CHAPTER 16 OF NFPA 101, THE
 REQUIREMENTS OF 16.2.11 SHALL BE/ARE MET AS IT RELATES
 TO SPECIAL MEANS OF EGRESS FEATURES - WINDOWS FOR
 RESCUE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW