| Date |
Text |
| 2010-01-19 12:12:50 | BUILDING P 10010084 |
| | ADD: 854 CONNISTON RD |
| | CONT: CATOE CONSTRUCTION |
| | TEL: (561)719-6395 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | JAN 19/2009 |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) PLANS ARE MISSING THE WIND DESIGN CRITERIA: 1603.1.4 |
| | WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 1.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 1.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | 1.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 1.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 1.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 2) PLEASE PROVIDE WIND PRESSURES FOR INTERIOR AND END |
| | ZONES, LOCATE END ZONES ON ELEVATIONS. 1603.1.4 / ASCE |
| | 7-05, CHAPTER 6 WIND. |
| | |
| | 3) PRODUCT APPROVAL SUBMITTED IS FOR SINGLE APPLICATION |
| | USAGE, SHEET 5 OF 7 INDICATES SEE SEPARATE APPROVAL FOR |
| | MULLIONS. RULE 9B-72 WILL REQUIRE EITHER A FL STATE |
| | APPROVAL OR MIAMI-DADE NOA .PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE |
| | REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL |
| | SYSTEM. FOR INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) PERMIT APPLICATION VALUE FOR WINDOW REPLACEMENT IS |
| | LOW AVERAGES OUT TO APPROXIMATELY $ 227.00 FOR COST OF |
| | NEW WINDOW, DUMP FEES, WINDOW REMOVAL, NEW BUCKS AND |
| | INSTALLATION OF NEW WINDOWS. |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 6) PLEASE NOTE THE SUBMITTED PLANS INDICATE A CHANGE OF |
| | OCCUPANCY FOR THIS BUILDING. THE LAST PERMITTED WORK |
| | INDICATES THIS STRUCTURE WAS A CHURCH WITH ASSOCIATED |
| | OFFICES AND SUNDAY SCHOOL ROOMS (A-3 OCCUPANCY). THE |
| | NEW OCCUPANCY WILL BE DAY CARE A SEPARATE PERMIT WILL |
| | NEED TO APPLY FOR THE CHANGE OF OCCUPANCY. THE PORTION |
| | THAT AFFECTS THIS WINDOW PERMIT IS SECTION 905.1 OF THE |
| | EXISTING BUILDING CODE 2007 FBC. MEANS OF EGRESS IN |
| | PORTIONS OF BUILDINGS UNDER-GOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH SECTION 912 OF THE |
| | EXISTING BUILDING CODE. |
| | |
| | 912.4.2 EXISTING BUILDING CODE. MEANS OF EGRESS FOR |
| | CHANGE OF USE TO EQUAL OR LOWER HAZARD CATEGORY. WHEN A |
| | CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO AN EQUAL |
| | OR LESSER HAZARD CATEGORY (HIGHER NUMBER) AS SHOWN IN |
| | TABLE 912.4, EXISTING ELEMENTS OF THE MEANS OF EGRESS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 805 FOR |
| | THE NEW OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR |
| | CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING . |
| | |
| | THE REMOVAL AND REPLACEMENT ENACTS SECTION: |
| | 1034.6 FL BLD CODE BUILDING- DAYCARE, SPECIAL MEANS OF |
| | EGRESS FEATURES. EVERY ROOM OR SPACE NORMALLY SUBJECT |
| | TO CLIENT OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE |
| | AT LEAST ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE AND |
| | VENTILATION. SUCH WINDOW SHALL BE OPERABLE FROM THE |
| | INSIDE WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A |
| | CLEAR OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN |
| | WIDTH, 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE |
| | FEET (0.53 M2) IN AREA (VENT ).. THE BOTTOM OF THE |
| | OPENING SHALL BE NOT MORE THAN 44 INCHES (1118 MM) |
| | ABOVE THE FLOOR. THE CLEAR OPENING SHALL PERMIT A |
| | RECTANGULAR SOLID, WITH A MINIMUM WIDTH AND HEIGHT THAT |
| | PROVIDES THE REQUIRED 5.7 SQUARE FOOT (0.53 M2) OPENING |
| | AND A MINIMUM DEPTH OF 20 INCHES (8 MM), TO PASS FULLY |
| | THROUGH THE OPENING. |
| | |
| | EXCEPTIONS: |
| | |
| | 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 2. WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| | TO THE OUTSIDE OF THE BUILDING. |
| | |
| | THE CLASSROOM # 1,4, 7 & 9 DO NOT HAVE DOOR WAYS THAT |
| | LEAD DIRECTLY TO THE EXTERIOR, REQUIRING THE LARGER 5.7 |
| | VENTED WINDOW OPENING. |
| | |
| | THERE ARE OTHER ISSUES THAT WILL NEED TO BE ADDRESSED |
| | WHEN THE CHANGE OF OCCUPANCY PERMIT WILL NEED TO |
| | ADDRESS. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |