Plan Review Notes
Plan Review Notes For Permit 10010072
Permit Number 10010072
Review Stop E
Sequence Number 1
Notes
Date Text
2010-01-20 08:27:18 
 ** DENIED *
  
  
 1) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK LISTED ON PLANS IS LOW. BASED ON THE PLANS THE
 WORK FOR ALL LABOR, MATERIALS, DESIGN COST AND
 EQUIPMENT NEEDS TO BE INCLUDED.
 THE SITE WALL , GATES, ELECTRICAL, LOW VOLTAGE WOULD BE
 UNDER SEPARATE PERMITS. PLEASE EXPLAIN IF THE SCOPE ON
 APPLICATION AND SCOPE ON PLANS IS SEPARATE.
 FBC 108.3 AS ADOPTED BY THE CITY OF WEST PALM BEACH
  
 2) NOTE: THERE ARE NO RELEVANT CODES ON PLANS AND
 INSUFFICIENT ELECTRICAL INFORMATION. PLANS STATES THERE
 ARE FOUR SPARE CIRCUITS HOWEVER PROVIDE NO INFORMATION
 ON BRANCH CIRCUIT SIZES, MOTOR LOADS, OVER CURRENT
 PROTECTION ETC.
 LOW VOLTAGE SCOPE DOES NOT INCLUDE WIRING METHODS IN
 WET LOCATIONS.
 PLEASE KNOW THAT AS OF OCTOBER 1ST, 2009 THE STATE AND
 FLORIDA BUILDING CODE ADOPTED THE 2008 NEC/ NFPA-70.
 PLEASE PROVIDE ELECTRICAL INFORMATION FOR ALL WIRING
 METHODS AND CONDUCTOR SIZES. 310.16, 240.4
 PLEASE INCLUDE VOLTAGE DROP CALCULATIONS. FBC
 13-413.AB1
 PLEASE INCLUDE COMPLETED PANEL SCHEDULES WITH LOADS OF
 EXISTING AND NEW. 408.4, 220.
 PLEASE SEE NEC 250 FOR GROUNDING. PLEASE SEE 250.122
 FOR SIZING OF EQUIPMENT GROUNDING CONDUCTORS.
  
  
 ** AS THERE IS SOME INFORMATION NOT YET SUBMITTED THERE
 MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  