| Plan Review Notes For Permit 10010071 |
| Permit Number |
10010071 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-07 09:31:45 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PROVIDE PRODUCT APPROVAL FOR FLAT ROOF TO BE USED. | | | NO INFORMATION WAS SUBMITTED. | | | | | | 2- CLEARLY MARK ON PRODUCT APPROVAL SPECIFIC APPROVED | | | ASSEMBLY AND BASE SHEET FASTENING OPTION TO BE USED TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | | ***NOTE 1: PROVIDE RAS 117 CALCULATIONS FOR NAIL | | | ENHANCING AT PERIMETER AND CORNER AREAS IF SELECTED | | | ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7. (CHECK | | | PRODUCT APPROVAL SUBMITTED TO SEE IF RAS 117 | | | CALCULATIONS NEED TO BE SIGNED AND SEALED). IF SELECTED | | | ASSEMBLY IS LIMITED BY GENERAL LIMITATION #9, THEN IT | | | MAY NOT BE USED IN THIS BUILDING IF THE DESIGN | | | PRESSRUES ASRE TOO LOW. | | | ***NOTE 2: BUILDING IS LOCATED ON EXPOSURE "C". TAKE | | | THIS INTO CONSIDERATION WHEN DOING THE RAS 117 | | | CALCULATIONS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|