| Plan Review Notes For Permit 10010061 |
| Permit Number |
10010061 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-02-01 16:21:01 | ** DENIED REVIEW * | | | | | | 1) NOTE: NO DESIGN CODES ON PLANS FOR PERMIT | | | APPLICATION MADE AFTER OCTOBER 1ST, 2009. | | | SHOULD HAVE THE FOLLOWING AT A MINIMUM. | | | 2008 NFPA-70 | | | | | | 2) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS. | | | FOR EXAMPLE: SHEET 8 STATES TO SEE SHEET #9 FOR | | | MODIFIED ELECTRICAL POWER PANEL HOWEVER SHEET #9 HAS NO | | | ELECTRICAL INFORMATION. | | | PLEASE SUBMIT CIRCUITING, PANELS, LOADS, INFORMATION ON | | | LIGHT POLES, BRANCH CIRCUITS, SIZES FOR CONDUCTORS, | | | BREAKERS ETC.ETC. | | | 220,215.5.230, 225, 408.4, 310.16 | | | | | | SECTIONS GIVEN IN GENERAL AS PLANS ARE NOT ENTIRELY | | | CLEAR FOR ELECTRICAL SCOPE OF WORK. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|