| 2010-01-21 16:56:53 | |
| | ** PROVISO ** |
| | |
| | ** REVISE THE FOLLOWING BEFORE ROUGH. SUBMIT PLANS AND |
| | BE SURE PLANS ARE ON-SITE FOR INSPECTION. |
| | |
| | |
| | 1) NOTE: PLANS ARE REFERENCED TO THE 2005 NEC. ALL PER |
| | ALL PROJECTS SUBMITTED FOR PERMIT AFTER OCTOBER 1ST, |
| | 2009 IS UNDER THE 2008 NEC. |
| | |
| | 2) NOTE: RISER DOES INCLUDE A PANEL L1 HOWEVER NO PANEL |
| | SCHEDULE FOR PANEL L WAS SUBMITTED. CAN NOT VERIFY SIZE |
| | OF FEEDER AND OVER CURRENT PROTECTION TO L1. |
| | 240.4,310.16,408.4 ETC |
| | CAN NOT VERIFY ADJUSTED LOADS ON PANEL L. |
| | 220,220.12,220.14,220.42,220.44 ETC. CONTINUOUS LOADS |
| | PER 215.3,230.42 ETC |
| | CAN NOT VERIFY TAPPED CONDUCTORS FROM TRANSFORMER |
| | TERMINATING IN OVER CURRENT PROTECTION PER 240.21, AND |
| | 408.36. PANEL L1 IS A MLO PANEL. |
| | |
| | 3) NOTE: ALL MINIMUM LEVELS FOR HORNS, STROBE FOR ADA |
| | COMPLIANCE NEEDS TO BE SHOWN. FOR EXAMPLE: STATING |
| | STROBES TO MEET ADA COMPLIANCE DOES NOT PROVIDE MINIMUM |
| | INFORMATION FOR COMPLIANCE. THIS SHOULD STATE MINIMUM |
| | CD OR CANDELA 75 OR WORDS TO THAT AFFECT. THE SAME FOR |
| | SOUNDING DEVICES AND LOCATIONS FOR DB LEVELS. |
| | ALTHOUGH THE FIRE ALARM WILL BE UNDER A SEPARATE PERMIT |
| | THE BASE PLANS IS REQUIRED TO SHOWN BASE DESIGN INTENT. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |