2010-01-21 16:56:53 
 ** PROVISO **
  
 ** REVISE THE FOLLOWING BEFORE ROUGH. SUBMIT PLANS AND
 BE SURE PLANS ARE ON-SITE FOR INSPECTION.
  
  
 1) NOTE: PLANS ARE REFERENCED TO THE 2005 NEC. ALL PER
 ALL PROJECTS SUBMITTED FOR PERMIT AFTER OCTOBER 1ST,
 2009 IS UNDER THE 2008 NEC.
  
 2) NOTE: RISER DOES INCLUDE A PANEL L1 HOWEVER NO PANEL
 SCHEDULE FOR PANEL L WAS SUBMITTED. CAN NOT VERIFY SIZE
 OF FEEDER AND OVER CURRENT PROTECTION TO L1.
 240.4,310.16,408.4 ETC
 CAN NOT VERIFY ADJUSTED LOADS ON PANEL L.
 220,220.12,220.14,220.42,220.44 ETC. CONTINUOUS LOADS
 PER 215.3,230.42 ETC
 CAN NOT VERIFY TAPPED CONDUCTORS FROM TRANSFORMER
 TERMINATING IN OVER CURRENT PROTECTION PER 240.21, AND
 408.36. PANEL L1 IS A MLO PANEL.
  
 3) NOTE: ALL MINIMUM LEVELS FOR HORNS, STROBE FOR ADA
 COMPLIANCE NEEDS TO BE SHOWN. FOR EXAMPLE: STATING
 STROBES TO MEET ADA COMPLIANCE DOES NOT PROVIDE MINIMUM
 INFORMATION FOR COMPLIANCE. THIS SHOULD STATE MINIMUM
 CD OR CANDELA 75 OR WORDS TO THAT AFFECT. THE SAME FOR
 SOUNDING DEVICES AND LOCATIONS FOR DB LEVELS.
 ALTHOUGH THE FIRE ALARM WILL BE UNDER A SEPARATE PERMIT
 THE BASE PLANS IS REQUIRED TO SHOWN BASE DESIGN INTENT.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  