| Plan Review Notes For Permit 10010042 |
| Permit Number |
10010042 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-06 10:09:45 | DENIED | | | REFERENCE: | | | FBC-2007 RESIDENTIAL | | | FBC-2007 EXISTING BUILDING | | | FBC-2007 CHAPTER 1 | | | | | | 1. SHT A1 DETAIL 1 SHOWS THE NEW BATHROOM AS 6'4" WIDE. | | | WITH THE SHOWER BEING 30" WIDE AND MOST W/C'S BEING 28" | | | OR MORE IN LENGTH, THAT LEAVES ABOUT 18" CLEARANCE IN | | | FRONT OF THE W/C. MINIMUM CLEARACE REQUIRED IS 21 | | | INCHES PER FIGURE R307.1. | | | | | | 2. NOTE: SHT A1 DETAIL 1 SHOWS THE BATHROOM AS 4' DEEP. | | | THE LAV AND W/C CLEARANCES SHALL COMPLY WITH FIGURE | | | R307.1. NOT KNOWING THE MAKE AND MODEL OF THE BATHROOM | | | FIXTURES, (W/C & LAV), THE CLEARANCES WILL BE REQUIRED | | | TO BE MET AT FINAL INSPECTION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|