| 2010-01-07 10:07:58 | 2007 FBC W/2009 REVISIONS |
| | CONVERT GARAGE TO BED AND BATH ROOMS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. 561-233-5025 |
| | |
| | 2) THE BUILDING CODE SPECIFIED ON SHEET AO IS |
| | INCORRECT. THE 2007 FLORIDA BUILDING CODE WITH 2009 |
| | REVISIONS IS THE APPLICABLE CODE. |
| | |
| | 3) THE LEVEL OF ALTERATION SPECIFIED IS INCORRECT. THIS |
| | IS A LEVEL 2 ALTERATION PER FBC EXISTING BUILDING 404.1 |
| | |
| | 4) THE ENERGY CALCULATION FORMS THAT WERE SUBMITTED |
| | HAVE BEEN CHANGED BY THE 2009 REVISIONS TO THE 2007 |
| | FBC. THE NEW FORM IS 1100B-08. |
| | |
| | 5) SPECIFY THE INSULATION AT THE WALL BETWEEN THE |
| | STORAGE AREA AND THE CONDITIONED SPACE ON THE THE |
| | PLANS. FBC CHAPTER 13 |
| | |
| | 6) SPECIFY THE INSULATION FOR THE UNDER FLOOR SPACE ON |
| | THE PLANS. FBC CHAPTER 13 |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R 408.2 FOR UNDER FLOOR |
| | VENTILATION OR R408.3 FOR UNVENTED CRAWL SPACE AND FBC |
| | R 408.4 FOR UNDER FLOOR ACCESS. |
| | |
| | 8) THE WINDOW BUCK DETAIL ON SHEET S1 DOES NOT SPECIFY |
| | THE SPACING FOR THE FASTENERS. PLEASE SPECIFY SPACING |
| | ON THE PLANS. |
| | |
| | 9) THE VALUE OF THE WORK ON THE APPLICATION IS TOO LOW. |
| | THE VALUE OF WORK IS TO INCLUDE ALL LABOR, MATERIAL, |
| | DESIGN COSTS, SUB-CONTRACTORS, PROFIT AND OVERHEAD AS |
| | WOULD BE CHARGED BY A CONTRACTOR FOR THE SCOPE OF WORK |
| | BEING PROPOSED. PLEASE ADJUST THE VALUE TO REFLECT ALL |
| | COSTS. FBC 108.3 |
| | |
| | 10) PLEASE RESPOND TO COMMENTS IN WRITING. PLEASE |
| | INDICATE HOW THE COMMENTS HAVE BEEN ADDRESSED IN THE |
| | RESPONSE. |
| | |