| Plan Review Notes For Permit 10010026 |
| Permit Number |
10010026 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-01-12 13:54:51 | REVISION SECOND CHECKLIST. | | | | | | 1- PRODUCT APPROVALS SUBMITTED ARE FOR SINGLE HUNG | | | WINDOWS AND FIXED WINDOWS. ORIGINAL PRODUCT APPROVALS | | | AND PLANS SHOWED ONLY CASEMENT WINDOWS. NEED TO REVISE | | | PLANS TO SHOW WINDOW SIZES TO VERIFY COMPLIANCE WITH | | | THE EGRESS REQUIREMENTS OF SEC. R310 OF 2007 FLORIDA | | | RESIDENTIAL CODE (COMMENT NOT ADDRESSED AT ALL). | | | REVISED PLANS TO SHOW EXISTING BEDROOM WINDOWS SIZES | | | AND PROPOSED WINDOW SIZES TO VERIFY COMPLIANCE WITH THE | | | MINIMUM REQUIRED CLEAR OPENINGS. | | | ***NOTE: A MAXIMUM OF 5% REDUCTION IN THE CLEAR OPENING | | | DIMENSION WILL BE ALLOWED. SEC. 604.1 OF 2007 FLORIDA | | | BUILDING CODE-EXISTING. | | | | | | 2- WINDOW MULLION PRODUCT APPROVAL. CLEARLY MARK ON | | | MULLION PRODUCT APPROVALS SPECIFIC MULLION SIZE AND | | | ANCHORS TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. SEC. | | | R301 OF 2007 FLORIDA RESIDENTIAL CODE (COMMENT NOT | | | ADDRESSED AT ALL). | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|