Plan Review Notes
Plan Review Notes For Permit 09120583
Permit Number 09120583
Review Stop P
Sequence Number 1
Notes
Date Text
2010-01-05 16:14:48DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 11
 FBC-2007 CHAPTER 1
 FBC-2007 PLUMBING
  
 1. SECTION 906.1 ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2. SECTION 11-4.1.3(11) IF TOILET ROOMS ARE PROVIDED,
 THEN EACH PUBLIC AND COMMON USE TOILET ROOM SHALL
 COMPLY WITH SECTION 11-4.22. IF BATHING ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM
 SHALL COMPLY WITH SECTION 11-4.23. SUBMIT DETAILS FOR
 THE TOILET ROOM AND THE BATHROOM SHOWING COMPLIANCE
 WITH SECTIONS 11-4.22 & 11-4.23 WITH ALL SUBSECTIONS.
  
 3. SHT C1 GENERAL NOTES 01 INDICATES THE PROJECT WAS
 DESIGNED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE
 2007 RESIDENTIAL EDITION. ALSO INDICATED ON THIS SHEET
 IS A CHANGE OF OCCUPANCY/USE FROM RESIDENTIAL TO
 BUSINESS. AS A BUSINESS OCCUPANCY, THE DESIGN SHALL BE
 IN ACCORDANCE WITH THE FLORIDA BUILDING CODE BUILDING.
  
 4. THE SINK IN THE LOUNGE SHALL BE ACCESSIBLE PER
 SECTION 906.1 AND 11-4.24. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS.
  
 5. SHT A-1 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. PLEASE SHOW THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAIN AND SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 6. SHTS A-1 & P2.01 INDICATE THE WATER SUPPLY TO THE
 SHOWER TO BE TERMINATED AND CAPPED OFF. PER SECTION
 1002.4, WHERE A TRAP SEAL IS SUBJECT TO LOSS BY
 EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. A TRAP SEAL PRIMER VALVE SHALL CONFORM TO
 ASSE 1018 OR ASSE 1044.
  
 7. A RZPV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved