| Date |
Text |
| 2010-01-05 16:14:48 | DENIED |
| | REFERENCE: |
| | FBC-2007 EXISTING BUILDING |
| | FBC-2007 CHAPTER 11 |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 PLUMBING |
| | |
| | 1. SECTION 906.1 ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| | UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| | BUILDING. |
| | |
| | 2. SECTION 11-4.1.3(11) IF TOILET ROOMS ARE PROVIDED, |
| | THEN EACH PUBLIC AND COMMON USE TOILET ROOM SHALL |
| | COMPLY WITH SECTION 11-4.22. IF BATHING ROOMS ARE |
| | PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM |
| | SHALL COMPLY WITH SECTION 11-4.23. SUBMIT DETAILS FOR |
| | THE TOILET ROOM AND THE BATHROOM SHOWING COMPLIANCE |
| | WITH SECTIONS 11-4.22 & 11-4.23 WITH ALL SUBSECTIONS. |
| | |
| | 3. SHT C1 GENERAL NOTES 01 INDICATES THE PROJECT WAS |
| | DESIGNED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE |
| | 2007 RESIDENTIAL EDITION. ALSO INDICATED ON THIS SHEET |
| | IS A CHANGE OF OCCUPANCY/USE FROM RESIDENTIAL TO |
| | BUSINESS. AS A BUSINESS OCCUPANCY, THE DESIGN SHALL BE |
| | IN ACCORDANCE WITH THE FLORIDA BUILDING CODE BUILDING. |
| | |
| | 4. THE SINK IN THE LOUNGE SHALL BE ACCESSIBLE PER |
| | SECTION 906.1 AND 11-4.24. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS. |
| | |
| | 5. SHT A-1 A DRINKING FOUNTAIN IS REQUIRED PER TABLE |
| | 403.1. PLEASE SHOW THE LOCATION OF THE REQUIRED |
| | DRINKING FOUNTAIN AND SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 6. SHTS A-1 & P2.01 INDICATE THE WATER SUPPLY TO THE |
| | SHOWER TO BE TERMINATED AND CAPPED OFF. PER SECTION |
| | 1002.4, WHERE A TRAP SEAL IS SUBJECT TO LOSS BY |
| | EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| | INSTALLED. A TRAP SEAL PRIMER VALVE SHALL CONFORM TO |
| | ASSE 1018 OR ASSE 1044. |
| | |
| | 7. A RZPV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO |
| | THE BUILDING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |