| 2010-01-14 01:22:58 | *****DENIED***** |
| | |
| | 01. PLANS NOT SIGNED AND SEALED BY THE |
| | ENGINEER/ARCHITECT OF RECORD. |
| | |
| | 02. THE POINT OF COMPASS SHOWN ON SHEET SP1 IS |
| | INCORRECT. THE PROJECT SITE IS NORTH OF 10TH STREET, |
| | NOT SOUTH AS INDICATED BY THE POINT OF COMPASS. |
| | |
| | 03. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 04. PROVIDE THE PRESCRIPTIVE STRENGHTS FOR THE |
| | HANDRAILS AND GUARDRAILS OF THE STAIRS. |
| | |
| | 05. ON SHEET A2, DISPLAY THE ADDRESS NUMBERS ON THE |
| | APPROPIATE EXTERION ELEVATION WHICH FRONTS NORTH OLIVE |
| | AVENUE. AS PER LOCAL CODES, ADDRESS NUMBERS SHALL BE NO |
| | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| | WIDTH/STROKE. |
| | |
| | 06. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE |
| | REFERENCED. SINCE THIS IS A CHANGE OF OCCUPANCY, |
| | CHAPTER 38 (NEW BUSINESS OCCUPANCY) OF NFPA 101 SHALL |
| | BE REFERENCED. |
| | |
| | 07. VERIFY THAT STAIRS AS PER 7.2.2 AND RAMPS AS PER |
| | 7.2.5 ARE IN COMPLIANCE. |
| | |
| | 08. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS |
| | AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | SPECIFY INTERIOR FLOOR FINISH IN COMPLIANCE WITH |
| | 10.2.7.1 OR 10.2.7.2, AS APPLICABLE. |
| | |
| | 09. SHOW THE LOCATION OF THE PORTABLE FIRE |
| | EXTINGUISHERS WHICH SATISFY THE 75" TRAVEL DISTANCE. |
| | |
| | 10. PLANS INDICATE TWO STORAGE ROOMS ON THE SECOND |
| | FLOOR. IDENTIFY THE HAZARD OF THE CONTENTS IN THE |
| | STORAGE ROOMS CLASSIFIED AS LOW, ORDINARY, OR HIGH. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE THE COMMENTS HAVE BEEN |
| | ADDRESSED ON THE PLANS |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |