| Plan Review Notes For Permit 09120546 |
| Permit Number |
09120546 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-31 07:41:09 | 1. THE FIRE ALARM SYSTEM AND COMPONENTS ARE TO BE | | | INSTALLED IN ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE | | | ALARM CODE. | | | | | | 2. THE ENTIRE SYSTEM IS TO BE TESTED WITH THIS OFFICE | | | UPON COMPLETION. | | | | | | 3. THE EXISTING FIRE ALARM EQUIPMENT SHALL ALSO BE IN | | | GOOD WORKING ORDER. | | | | | | 4. THE ENTIRE INSTALLATION IS SUBJECT TO FIELD | | | INSPECTION AND APPROVAL. | | | | | | 5. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL | | | LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION | | | SERVICE. | | | | | | 6. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT | | | LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. | | | | | | | | | APPROVED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|