| Plan Review Notes For Permit 09120539 |
| Permit Number |
09120539 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-29 15:57:39 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ACCORDING TO THE MIAMI-DADE WEBSITE MODIFIED BITUMEN | | | 07-1203.01 IS SUPERSEDED. GO TO MIAMI-DADE WEBSITE AND | | | PROVIDE CURRENT NOA. | | | | | | 2- GAF MODIFIED BITUMEN NOA'S REQUIRE SIGNED AND SEALED | | | RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER | | | AND CORNER AREAS. SEE GENERAL LIMITATION #7 ON LAST | | | PAGE OF NOA SUBMITTED. NEED TO PROVIDE SIGNED AND | | | SEALED RAS 117 CALCULATIONS. ***NOTE: DESIGN | | | PROFESSIONAL DOING THE CALCULATIONS TO TAKE INTO | | | CONSIDERATION THAT ACCORDING TO THE 2009 REVISIONS THIS | | | BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". | | | | | | 3- CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY | | | IS GOING TO BE INSTALLED. AND, WHICH BASE SHEET | | | FASTENING OPTION IS GOING TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF | | | 2007 FLORIDA RESIDENTIAL CODE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|