Plan Review Notes
Plan Review Notes For Permit 09120539
Permit Number 09120539
Review Stop B
Sequence Number 1
Notes
Date Text
2009-12-29 15:57:39RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE MIAMI-DADE WEBSITE MODIFIED BITUMEN
 07-1203.01 IS SUPERSEDED. GO TO MIAMI-DADE WEBSITE AND
 PROVIDE CURRENT NOA.
  
 2- GAF MODIFIED BITUMEN NOA'S REQUIRE SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER
 AND CORNER AREAS. SEE GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA SUBMITTED. NEED TO PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS. ***NOTE: DESIGN
 PROFESSIONAL DOING THE CALCULATIONS TO TAKE INTO
 CONSIDERATION THAT ACCORDING TO THE 2009 REVISIONS THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B".
  
 3- CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY
 IS GOING TO BE INSTALLED. AND, WHICH BASE SHEET
 FASTENING OPTION IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved