2010-01-11 14:37:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO INFORMATION WAS PROVIDED REGARDING THE PROPOSED
 OVEN/FURNACE. PROVIDE MANUFACTURER'S SUBMITTAL DATA AND
 INSTALLATION INSTRUCTIONS PER FBC-M 304.1.
  
 2. NO INFORMATION WAS PROVIDED REGARDING THE PROPOSED
 EXHAUST DUCTWORK. PROVIDE TYPE AND SIZE OF DUCT TO BE
 USED IN ACCORDANCE WITH FBC-M 501.1.
  
 3. PLANS APPEAR TO INDICATE EXHAUST FANS AND DUCTWORK
 BEING INSTALLED OUTDOORS. FANS AND DUCT SHALL BE
 DESIGNED AND INSTALLED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12. PROVIDE MANUFACTURER'S
 DATA FOR THE WIND RESISTANCE CHARACTERISTICS OF THE
 FANS AND WIND RESISTANT INSTALLATION DETAILS FOR THE
 FANS AND THE DUCTWORK.
  
 4. PLANS SHOW LOUVERS ON THE SOUTH WALL OF THE
 BUILDING. ARE THESE LOUVERS NEW OR EXISTING? PLEASE
 INDICATE ON THE PLANS WHAT IS NEW AND WHAT IS EXISTING
 TO DEMONSTRATE THE EXACT SCOPE OF WORK PER FBC-B 106.1.
  
 5. IF LOUVERS ARE NEW, PROVIDE PRODUCT APPROVALS FOR
 LOUVERS AS REQUIRED PER FBC-B 106.3.3 AND FAC RULE
 9B-72.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]