| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 |
| | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING |
| | |
| | 1} THE CODE ARTICLES REFERENCED ON SHEET E1 ARE |
| | INCORRECT, SEE ABOVE FOR THE CORRECT CODES. |
| | |
| | 2} THE RISER DIAGRAM ON SHEET E3 APPEARS TO HAVE THE |
| | GROUNDING ELECTRODE CONDUCTOR ATTACHED TO A GROUND |
| | BETWEEN THE CT AND THE TRANSFORMER. 250.24(A)(1) |
| | GENERAL THE CONNECTION SHALL BE MADE AT ANY ACCESSIBLE |
| | POINT FROM THE LOAD END OF THE SERVICE DROP OR SERVICE |
| | LATERAL TO AND INCLUDING THE TERMINAL OR BUS TO WHICH |
| | THE GROUNDED SERVICE CONDUCTOR IS CONNECTED AT THE |
| | SERVICE DISCONNECTING MEANS. |
| | |
| | 3} THE 1600 AMP MCB MUST HAVE GROUND FAULT PROTECTION |
| | PER 230.95 GROUND-FAULT PROTECTION OF EQUIPMENT |
| | GROUND-FAULT PROTECTION OF EQUIPMENT SHALL BE PROVIDED |
| | FOR SOLIDLY GROUNDED WYE ELECTRICAL SERVICES OF MORE |
| | THAN 150 VOLTS TO GROUND BUT NOT EXCEEDING 600 VOLTS |
| | PHASE-TO-PHASE FOR EACH SERVICE DISCONNECT RATED 1000 |
| | AMPERES OR MORE. THE GROUNDED CONDUCTOR FOR THE SOLIDLY |
| | GROUNDED WYE SYSTEM SHALL BE CONNECTED DIRECTLY TO |
| | GROUND WITHOUT INSERTING ANY RESISTOR OR IMPEDANCE |
| | |
| | 4} THE OCP AND 1/0 CONDUCTORS ARE INCORRECT FOR THE |
| | 112.5 KVA TRANSFORMER. SEE 450.5(A)(2) (125%). ALSO |
| | THERE ARE 4 CONDUCTORS LISTED AT THAT SIZE WHEN THERE |
| | SHOULD ONLY BE THREE AND A GROUNDING CONDUCTOR. |
| | |
| | 5} THE ELECTRICAL CONTRACTOR NEEDS TO SIGN THE PERMIT |
| | APPLICATION UNDER "CONTRACTOR SIGNATURE PORTION ON THE |
| | BACK OF THE PERMIT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |