| 2009-12-29 14:22:17 | BUILDING PLAN REVIEW |
| | PERMIT: 09120535 |
| | ADD: 3220 45TH ST |
| | CONT: GARY R BROWN |
| | TEL: (954)214-1533 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | DEC. 29/ 2009 |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS |
| | PERMIT. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | NOTE THIS IS A CHANGE OF OCCUPANCY FROM A MERCANTILE/ |
| | WAREHOUSE TO A F2 FACTORY- INDUSTRIAL USAGE. |
| | |
| | 2 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR A NEW |
| | CERTIFICATE OF OCCUPANCY SINCE THERE WAS A CHANGE IN |
| | OCCUPANCY: |
| | 2A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | |
| | 2B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | |
| | 2C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER5, |
| | TABLE 503 (ALLOWABLE HEIGHT AND AREA) . |
| | |
| | 2D) THE OCCUPANT LOAD, SEE 1004. |
| | |
| | 2E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | |
| | 2F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED ( AREA |
| | INCREASES) |
| | |
| | 2G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | |
| | 2H ) SQ. FT. FOOTPRINT OF BUILDING. |
| | |
| | 3) FL EXISTING BLDG CODE 912.1.1 COMPLIANCE WITH |
| | CHAPTER 8. THE REQUIREMENTS OF CHAPTER 8 SHALL BE |
| | APPLICABLE THROUGHOUT THE BUILDING FOR THE NEW |
| | OCCUPANCY CLASSIFICATION BASED ON THE SEPARATION |
| | CONDITIONS SET FORTH IN SECTIONS 912.1.1.1 AND |
| | 912.1.1.2. |
| | |
| | 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT |
| | SEPARATION. WHERE A PORTION OF AN EXISTING BUILDING IS |
| | CHANGED TO A NEW OCCUPANCY CLASSIFICATION AND THAT |
| | PORTION IS NOT SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING WITH A FIRE-RATED WALL/CEILING HAVING A |
| | FIRE-RESISTANCE RATING AS REQUIRED IN THE FLORIDA |
| | BUILDING CODE FOR THE SEPARATE OCCUPANCY, THE ENTIRE |
| | BUILDING SHALL COMPLY WITH ALL OF THE REQUIREMENTS OF |
| | CHAPTER 8 APPLIED THROUGHOUT THE BUILDING FOR THE MOST |
| | RESTRICTIVE OCCUPANCY CLASSIFICATION IN THE BUILDING |
| | AND WITH THE REQUIREMENTS OF THIS CHAPTER. |
| | |
| | 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH |
| | SEPARATION. WHERE A PORTION OF AN EXISTING BUILDING |
| | THAT IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION AND |
| | THAT PORTION IS SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING WITH FIRE BARRIERS HAVING A FIRE-RESISTANCE |
| | RATING AS REQUIRED IN THE FLORIDA BUILDING CODE FOR THE |
| | SEPARATE OCCUPANCY, THAT PORTION SHALL COMPLY WITH ALL |
| | THE REQUIREMENTS OF CHAPTER 8 FOR THE NEW OCCUPANCY |
| | CLASSIFICATION AND WITH THE REQUIREMENTS OF THIS |
| | CHAPTER. |
| | |
| | 4) SHEET E2 INDICATES 12???-0??? LOUVERS OVER TOP OF |
| | DOORS, IS THIS EXISTING OPENINGS OR ARE THEY NEW |
| | OPENINGS? |
| | |
| | 4A) IF NEW OPENINGS HOW IS THE MASONRY ABOVE BEING HELD |
| | IN PLACE? ARE THERE NEW COLUMNS? |
| | |
| | 4B) IF NEW OPENINGS THEN THE LOUVERS WILL NEED PRODUCT |
| | APPROVALS EITHER THE FLORIDA APPROVALS OR THE |
| | MIAMI-DADE NOA???S ARE ACCEPTABLE, FL ADMINISTRATIVE |
| | CODE RULE 9B-72 |
| | (31)( C ). |
| | |
| | 4C) IF NEW OPENINGS, PLEASE PROVIDE WIND DESIGN |
| | CRITERIA: 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 4C)1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 4C)2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 4C)3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 4C)4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 4C)5. COMPONENTS AND CLADDING. THE DESIGN WIND |
| | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE |
| | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS |
| | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 5) WILL EITHER A OVERHEAD CRANE OR CONVEYOR BE |
| | INSTALLED ADDING WEIGHT TO THE ROOF OR WALL REQUIRING |
| | ADDITIONAL LOADING AND ENGINEERING? 106.1.2. ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |