| 2010-01-13 14:03:34 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. SHOW ON PLANS THE MEANS AND LOCATION OF CONDENSATE |
| | DISPOSAL IN ACCORDANCE WITH FBC-M 307.2.1. |
| | |
| | 2. ELECTRICAL PLANS SHOW 3 HEAT PUMPS WHILE MECHANICAL |
| | PLANS SHOW 6 HEAT PUMPS PLUS 1 FUTURE 100% OUTSIDE AIR |
| | UNIT ON THE SAME PANEL. PLEASE COORDINATE MECHANICAL |
| | AND ELECTRICAL PLANS SHOWING HOW ALL APPLIANCES ARE TO |
| | BE PROVIDED WITH POWER IN ACCORDANCE WITH FBC-M 304.1. |
| | |
| | 3. HEAT PUMP SCHEDULE NOTE #5 CALLS FOR CONDENSATE |
| | PUMPS AT EACH HEAT PUMP. NO CONDENSATE PUMPS ARE SHOWN |
| | ON MECHANICAL FLOOR PLANS OR ELECTRICAL PLANS. PLEASE |
| | CLARIFY IN ACCORDANCE WITH FBC-M 307.2.1 AND 304.1. |
| | |
| | 4. OUTSIDE AIR CALCULATIONS STATE THEY ARE BASED ON |
| | TABLE 403.3 AND ASHRAE 62-01. THE ASHRAE |
| | STANDARDREFERENCED IS NOT A REFERENCED STANDARD IN THE |
| | 2007 FBC. CALCULATIONS ARE NOT IN COMPLIANCE WITH FBC-M |
| | SECTION 403. THERE IS NO 3-HOUR DIVERSITY RULE ALLOWED |
| | IN SECTION 403. PROVIDE FULL VENTILATION RATES AS |
| | REQUIRED BY TABLE 403.3. ALSO, SOME OUTSIDE AIR |
| | CALCULATIONS ARE INACCURATE. A CORRIDOR AND RECEPTION |
| | AREA HAVE DIFFERENT VENTILATION RATE REQUIREMENTS. THE |
| | RATE OF 20 CFM IS OK FOR CORRIDOR #1 BUT NOT ENOUGH FOR |
| | THE RECEPTION AREA. CORRIDOR CALCULATIONS SHALL BE |
| | BASED ON SQUARE FOOTAGE AND NOT OCCUPANT LOAD BASED ON |
| | TABLE 403.3. PLEASE MAKE ALL NECESSARY CORRECTIONS TO |
| | COMPLY WITH 403.3 OR CHANGE REFERENCE TO ASHRAE |
| | 62.1-2004 AND DEMONSTRATE COMPLIANCE WITH THAT |
| | STANDARD. DO NO REFERENCE BOTH 403.3 AND ASHRAE. SELECT |
| | ONE OR THE OTHER. |
| | |
| | 5. SHOW ALL HYDRONIC PIPING LOCATIONS ON PLANS IN |
| | ACCORDANCE WITH FBC-M 1201.1 AND FBC-B 106.3.5. |
| | |
| | 6. SUBMIT LOUVER PRODUCT APPROVAL DOCUMENTATION WITH |
| | WIND PRESSURE INFORMATIONAND INSTALLATION INSTRUCTIONS |
| | FOR BUILDING PLAN REVIEW IN ACCORDANCE WITH FBC-B |
| | 106.3.3. |
| | |