Plan Review Notes
Plan Review Notes For Permit 09120487
Permit Number 09120487
Review Stop M
Sequence Number 1
Notes
Date Text
2010-01-13 14:03:34REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SHOW ON PLANS THE MEANS AND LOCATION OF CONDENSATE
 DISPOSAL IN ACCORDANCE WITH FBC-M 307.2.1.
  
 2. ELECTRICAL PLANS SHOW 3 HEAT PUMPS WHILE MECHANICAL
 PLANS SHOW 6 HEAT PUMPS PLUS 1 FUTURE 100% OUTSIDE AIR
 UNIT ON THE SAME PANEL. PLEASE COORDINATE MECHANICAL
 AND ELECTRICAL PLANS SHOWING HOW ALL APPLIANCES ARE TO
 BE PROVIDED WITH POWER IN ACCORDANCE WITH FBC-M 304.1.
  
 3. HEAT PUMP SCHEDULE NOTE #5 CALLS FOR CONDENSATE
 PUMPS AT EACH HEAT PUMP. NO CONDENSATE PUMPS ARE SHOWN
 ON MECHANICAL FLOOR PLANS OR ELECTRICAL PLANS. PLEASE
 CLARIFY IN ACCORDANCE WITH FBC-M 307.2.1 AND 304.1.
  
 4. OUTSIDE AIR CALCULATIONS STATE THEY ARE BASED ON
 TABLE 403.3 AND ASHRAE 62-01. THE ASHRAE
 STANDARDREFERENCED IS NOT A REFERENCED STANDARD IN THE
 2007 FBC. CALCULATIONS ARE NOT IN COMPLIANCE WITH FBC-M
 SECTION 403. THERE IS NO 3-HOUR DIVERSITY RULE ALLOWED
 IN SECTION 403. PROVIDE FULL VENTILATION RATES AS
 REQUIRED BY TABLE 403.3. ALSO, SOME OUTSIDE AIR
 CALCULATIONS ARE INACCURATE. A CORRIDOR AND RECEPTION
 AREA HAVE DIFFERENT VENTILATION RATE REQUIREMENTS. THE
 RATE OF 20 CFM IS OK FOR CORRIDOR #1 BUT NOT ENOUGH FOR
 THE RECEPTION AREA. CORRIDOR CALCULATIONS SHALL BE
 BASED ON SQUARE FOOTAGE AND NOT OCCUPANT LOAD BASED ON
 TABLE 403.3. PLEASE MAKE ALL NECESSARY CORRECTIONS TO
 COMPLY WITH 403.3 OR CHANGE REFERENCE TO ASHRAE
 62.1-2004 AND DEMONSTRATE COMPLIANCE WITH THAT
 STANDARD. DO NO REFERENCE BOTH 403.3 AND ASHRAE. SELECT
 ONE OR THE OTHER.
  
 5. SHOW ALL HYDRONIC PIPING LOCATIONS ON PLANS IN
 ACCORDANCE WITH FBC-M 1201.1 AND FBC-B 106.3.5.
  
 6. SUBMIT LOUVER PRODUCT APPROVAL DOCUMENTATION WITH
 WIND PRESSURE INFORMATIONAND INSTALLATION INSTRUCTIONS
 FOR BUILDING PLAN REVIEW IN ACCORDANCE WITH FBC-B
 106.3.3.
  