| Plan Review Notes For Permit 09120487 |
| Permit Number |
09120487 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-04 11:26:50 | | | | PROVISO | | | | | | 1} THE EQUIPMENT GROUND TO THE METER AND BETWEEN THE | | | METER AND DISCONNECT ON THE RISER DIAGRAM CREATES A | | | PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE | | | REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE | | | TO BE RAN FROM THE FIRST MEANS OF DISCONNECT. 250.6. | | | | | | 2} 408.36(A) LIGHTING AND APPLIANCE BRANCH-CIRCUIT | | | PANELBOARD INDIVIDUALLY PROTECTED EACH LIGHTING AND | | | APPLIANCE BRANCH-CIRCUIT PANELBOARD SHALL BE | | | INDIVIDUALLY PROTECTED ON THE SUPPLY SIDE BY NOT MORE | | | THAN TWO MAIN CIRCUIT BREAKERS OR TWO SETS OF FUSES | | | HAVING A COMBINED RATING NOT GREATER THAN THAT OF THE | | | PANELBOARD.*** THE 200 AMP FUSES MUST BE 150 AMP IN THE | | | DISCONNECT. | | | | | | 3} THE HEAT PUMPS ON PANEL SCHEDULE "A" AND SHOWN ON | | | SHEET "E-1 DO NOT CORRELATE WITH THE HEAT PUMP SCHEDULE | | | ON SHEET M4.1. CORRELATE SAME , PLACE ON PLAN AND | | | RECALCULATE THE CONNECTED LOAD. 106.1.1 FBC | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|