2010-01-04 11:26:50 
 PROVISO
  
 1} THE EQUIPMENT GROUND TO THE METER AND BETWEEN THE
 METER AND DISCONNECT ON THE RISER DIAGRAM CREATES A
 PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE
 REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE
 TO BE RAN FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 2} 408.36(A) LIGHTING AND APPLIANCE BRANCH-CIRCUIT
 PANELBOARD INDIVIDUALLY PROTECTED EACH LIGHTING AND
 APPLIANCE BRANCH-CIRCUIT PANELBOARD SHALL BE
 INDIVIDUALLY PROTECTED ON THE SUPPLY SIDE BY NOT MORE
 THAN TWO MAIN CIRCUIT BREAKERS OR TWO SETS OF FUSES
 HAVING A COMBINED RATING NOT GREATER THAN THAT OF THE
 PANELBOARD.*** THE 200 AMP FUSES MUST BE 150 AMP IN THE
 DISCONNECT.
  
 3} THE HEAT PUMPS ON PANEL SCHEDULE "A" AND SHOWN ON
 SHEET "E-1 DO NOT CORRELATE WITH THE HEAT PUMP SCHEDULE
 ON SHEET M4.1. CORRELATE SAME , PLACE ON PLAN AND
 RECALCULATE THE CONNECTED LOAD. 106.1.1 FBC
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  