2010-02-24 11:09:45DENIED
 REFERENCE:
 FBC-2007 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORID STATUTES
  
 1. SHT 8 OF 10. CHANGES TO A DRAWING BY AN ENGINEER
 SHALL BE SIGNED, SEALED & DATED BY THE ENGINEER OF
 RECORD. SECTION 106.1, FAC 61G15-23/002 & FS 471.025
  
 2. SHT 8 OF 10 SANITARY RISER DIAGRAM DOES NOT MEET THE
 CODE REQUIREMENTS PER SECTION P3107.3.
  
 P3107.3 CONNECTION AT DIFFERENT LEVELS. WHERE THE
 FIXTURE DRAINS CONNECT AT DIFFERENT LEVELS, THE VENT
 SHALL CONNECT AS A VERTICAL EXTENSION OF THE VERTICAL
 DRAIN. THE VERTICAL DRAIN PIPE CONNECTING THE TWO
 FIXTURE DRAINS SHALL BE CONSIDERED THE VENT FOR THE
 LOWER FIXTURE DRAIN, AND SHALL BE SIZED IN ACCORDANCE
 WITH TABLE P3107.3. THE UPPER FIXTURE SHALL NOT BE A
 WATER CLOSET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.