| 2010-03-02 14:44:24 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ACCORDING TO THE 2009 REVISIONS SEC. R301.2.1.4.3 OF |
| | THE 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C" NOT "B". NEED TO REVISE THE |
| | DESIGN CRITERIA AND THE DESIGN PRESSURES ON SHEET #2 |
| | AND #7. (REPEAT COMMENT). |
| | |
| | 2- VALUATION DECLARED ON THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $3036.12 |
| | FOR UPDATED VALUATION, RADON FEES AND BALANCE OF PERMIT |
| | FEES. |
| | |
| | ***PAY BALANCE AT TIME OF PERMIT PICK UP. |
| | |
| | 3- MISSING COPY OF THE IMPACT FEES PAID RECEIPT. |
| | |
| | 4- PROVIDE 2 COPIES OF SOIL TEST REPORT. SEC. R401.4 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | ***ENGINEER RESPONSE LETTER STATES THAT THE ASSUMED |
| | SOIL BEARING CAPACITY IS 2000PSF. BUT, FOUNDATION PLAN |
| | AND WALL SECTION ON SHEET #6 STATES 2500PSF MIN. SOIL |
| | BEARING CAPACITY. REVISE PLANS AS REQUIRED TO REFLECT |
| | CORRECT DESIGN ASSUMPTIONS. |
| | |
| | 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR WINDOW MULLIONS. AND, CLEARLY MARK |
| | SPECIFIC MULLION SIZE AND FASTENERS TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. |
| | (THIS APPLIES TO THE EXISTING WINDOWS TO BE REPLACED. |
| | SEE ELEVATIONS). |
| | AND, ENGINEER OF RECORD TO REVIEW AND APPROVE IT IN |
| | WRITING. SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 6- SHEET #6: A) PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR BALCONY GUARDRAIL TO SHOW COMPLIANCE |
| | WITH TABLE R301.5 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | GUARDRAIL DESIGN INFORMATION WAS NOT PROVIDED. |
| | |
| | B) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR |
| | BALCONY UNDERSIDE CONSTRUCTION AND FASCIA BOARD AND |
| | SECOND FLOOR SOFFIT TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301. INFORMATION WAS NO |
| | PROVIDED. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712. |