| 2009-12-30 16:56:17 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ACCORDING TO THE 2009 REVISIONS SEC. R301.2.1.4.3 OF |
| | THE 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C" NOT "B". NEED TO REVISE THE |
| | DESIGN CRITERIA AND THE DESIGN PRESSURES ON SHEET #2 |
| | AND #7. |
| | |
| | 2- VALUATION DECLARED ON THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $3036.12 |
| | FOR UPDATED VALUATION, RADON FEES AND BALANCE OF PERMIT |
| | FEES. |
| | |
| | 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD. (561)233-5120) TO PAY THE |
| | IMPACT FEES. BRING BACK THE STAMPED PLANS AND COPY OF |
| | PAID RECEIPT. |
| | |
| | 4- PROVIDE 2 COPIES OF SOIL TEST REPORT. SEC. R401.4 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) SLIDING GLASS DOORS. NOA 07-0511.06 SUBMITTED |
| | EXPIRED ON NOVEMBER 11, 2009. NEED TO PROVIDE CURRENT |
| | NOA. |
| | |
| | B) WINDOW MULLIONS. AND, CLEARLY MARK SPECIFIC MULLION |
| | SIZE AND FASTENERS TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301. |
| | |
| | C) HARDIPLANK SIDING. |
| | |
| | D) BALCONY UNDERLAYMENT TO RECEIVE CERAMIC TILE. TO |
| | VERIFY COMPLIANCE WITH THE UPLIFT PRESSURES OF SEC. |
| | R301. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NO SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 7- SHEET #4: A) ATTIC ACCESS LOCATION DOESN'T COMPLY |
| | WITH SEC. R807.1. NEED TO PROVIDE ENOUGH CLEAR |
| | HEADROOM. REVISE LOCATION. |
| | |
| | B) SPECIFY ATTIC ACCESS. SEC. R807.1. |
| | |
| | C) REVISE BALUSTRADES NOTE: 42" RAILING HEIGHT NEEDS TO |
| | BE REVISED TO COMPLY WITH SEC. R311.5.6.1. (NOTE: |
| | RAILING AND GUARDRAIL ARE TWO DIFFERENT THINGS). |
| | |
| | 8- SHEET #5: A) SPECIFY FIREBLOCKING LOCATION AND |
| | MATERIAL ON STAIRS CROSS SECTION AS REQUIRED BY SEC. |
| | R602.1.2. |
| | |
| | B) REVISE RAILING HEIGHT ON STAIRS BALUSTRADE DETAIL TO |
| | COMPLY WITH SEC. R311.5.6.1. |
| | |
| | C) STAIRS BALUSTRADE DETAIL DOESN'T MATCH FLOOR PLANS. |
| | THERE IS A BEARING WALL ON THE HANDRAIL SIDE. REVISE AS |
| | REQUIRED. |
| | |
| | D) DETAIL A/5:: CLARIFY WHY THERE IS ONLY ONE ANCHOR |
| | FOR EACH 2X8 BOTTOM PLATE SEGMENT BETWEEN TRUSSES. THIS |
| | IS NOT A CONTINUOUS BOTTOM PLATE. THEREFORE, THE WAY |
| | THE ANCHORS ARE SPACED SHOW ONLY ONE ANCHOR PER |
| | SEGMENT. REVISE AS REQUIRED. |
| | |
| | E) PROVIDE COMPLETE SPECIFICATIONS FOR THE CONSTRUCTION |
| | OF THE STAIRS. SPECIFY MATERIAL AND PROVIDE DETAIL |
| | SHOWING COMPLIANCE WITH SEC. R311.5.3.3. |
| | |
| | 9- SECTION D/6 ON SHEET #6: A) SPECIFY SIZE AND |
| | LOCATION (SPACING) OF SOFFIT VENTS TO SHOW COMPLIANCE |
| | WITH SEC. R806. |
| | |
| | B) SPECIFY FIREBLOCKING LOCATION AND MATERIAL BY THE |
| | BALCONY AREA TO SHOW COMPLIANCE WITH SEC. R602.1.2. |
| | |
| | C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | BALCONY GUARDRAIL TO SHOW COMPLIANCE WITH TABLE R301.5. |
| | |
| | D) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR |
| | BALCONY UNDERSIDE CONSTRUCTION AND FASCIA BOARD AND |
| | SECOND FLOOR SOFFIT TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSRUES OF SEC. R301. |
| | |
| | 10- ROOF FRAMING PLAN ON SHEET #7. PROVIDE DETAIL |
| | SHOWING HOW ARE J1, J2 AND J3 TRUSSES SUPPORTED IF |
| | THERE IS NO BEAM. SEC. R301. |
| | |
| | 11- COMPLETE WITH A CHECK MARK THE CODE COMPLIANCE |
| | CHECKLIST ON PAGE 5 OF 5 OF THE ENERGY CALCULATIONS |
| | SUBMITTED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712. |