| 2010-03-04 09:56:04 | **PROVISO** | | | | | | 1. PROVIDE MANUFACTURER'S DATA FOR CONDENSING UNIT AND | | | ROOF CAP SHOWING THESE TO BE DESIGNED FOR WIND | | | RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. | | | | | | 2. PAGE M-2 AHU INSTALLATION DETAIL STILL CALLS FOR | | | CONDENSATE TO DISCHARGIN INTO HUB DRAIN. CONDENSATE | | | SHALL NOT DISCHARGE INTO SANITARY SEWER SYSTEM PER | | | FBC-M 307.2.1 AND CITY ORDINANCE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|