| Date |
Text |
| 2010-01-07 14:30:28 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 ADMIN. |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB CODE OF ORDINANCES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS, SHEET M 1 & ALL ELECTRICAL |
| | SHEETS. PER FAC 61G1-16.004(2)(6) THE FIRM LICENSE |
| | NUMBER, (CERTIFICATE OF AUTHORIZATION), AND PRINTED |
| | NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN |
| | THE TITLE BLOCK OF EACH SHEET. FS 481.2055. |
| | |
| | 2. SHEETS M 2, P 1 & P 2 A TITLE BLOCK MUST APPEAR ON |
| | ALL ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS AND |
| | SPECIFICATION IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TLEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | THE ABOVE SHEETS HAVE NO TITLE BLOCK AS REQUIRED. FS |
| | 481.2055. |
| | |
| | 3. SHT P 1 SHOWS CONDENSATE FROM HVAC-1 DRAINING TO |
| | MS-1. THIS IS NOT APPROVED PER CITY CODE ARTICLE III |
| | SECTION 90-124. THE CONDENSATE SHALL DRAIN FROM THE |
| | BUILDING SEPARATELY AND TERMINATE IN A DRYWELL, A STORM |
| | DRAIN, (RELIEF VENT REQUIRED AS CONDENSATE EXITS THE |
| | BUILDING), OR TO A PLANTED AREA. |
| | |
| | 4. SHTS P 1 & P 2 THE VENT FOR THE MOP SINK. PER |
| | SECTION 905.4 EVER DRY VENT SHALL RISE VERTICALLY TO A |
| | MINIMUM OF 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE |
| | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. THE PLANS |
| | SHOW THE VENT RUNNING HORIZONTALLY UNDER THE SLAB. |
| | |
| | 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM AS REQUIRED |
| | IN SECTION 106.3.5.1.3. SHOW ALL PIPE SIZE, VALVES AND, |
| | (WHERE REQUIRED BY SECTION 604.9) WATER HAMMER |
| | ARRESTORS). WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE |
| | CEILING. PDI-WH 201. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |