| Date |
Text |
| 2010-01-19 16:36:30 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGE M1 AND "MECHANIACL CODE NOTES" #5 CALLS FOR |
| | DUCT SMOKE DETECTORS TO BE INSTALLED ON THE RETURN |
| | DUCT. SMOKE DETECTORS SHALL BE INSTALLED IN THE SUPPLY |
| | AIR SYSTEM IN ACCORDANCE WITH FBC-M 606.2.1. |
| | |
| | 2. PAGE M1 SHOWS EXHAUST DUCTS LOCATED IN THE RETURN |
| | AIR PLENUM SPACE. EXHAUST DUCTS UNDER POSITIVE PRESSURE |
| | SHALL NOT BE LOCATED IN A PLENUM IN ACCORDANCE WITH |
| | FBC-M 601.5. |
| | |
| | 3. PAGE M1 SHOWS EF-3 TO NEW CURB AND ROOF CAP. ROOF |
| | CURB AND CAP SHALL BE DESIGNED AND INSTALLED FOR WIND |
| | RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. PROVIDE |
| | STRUCTURAL INSTALLATION DETAIL FOR THE NEW ROOF CURB |
| | AND MANUFACTURER'S DATA WITH INSTALLATION INSTRUCTIONS |
| | SHOWING WIND RESISTANCE CAPABILITIES OF THE PROPOSED |
| | ROOF CAP. |
| | |
| | 4. HVAC-1 CONDENSING UNIT IS PROPOSED FOR ROOF |
| | INSTALLATION. PROVIDE STRUCTURAL INSTALLATION DETAIL |
| | FOR WIND RESISTANT INSTALLATION OF CONDENSER IN |
| | ACCORDANCE WITH FBC-M 301.12. ALSO PROVIDE |
| | MANUFACTURER'S DATA SHOWING THE CONDENSER IS DESIGNED |
| | FOR WIND RESISTANCE. IF A PRE-ENGINEERED ROOF STAND IS |
| | USED, PROVIDE PRODUCT APPROVAL IN ACCORDANCE WITH FBC-B |
| | 106.3.3 AND FAC RULE 9B-72. |
| | |
| | 5. NEW CONDENSING UNIT ON THE ROOF SHALL COMPLY WITH |
| | THE REQUIREMENTS FOR GUARDS IF WITHIN 10 FEET OF THE |
| | ROOF EDGE IN ACCORDANCE WITH FBC-M 304.10. PERMANENT |
| | MEANS OF ACCESS MAY ALSO BE REQUIRED IN ACCORDANCE WITH |
| | FBC-M 306.5. PROVIDE ROOF PLAN SHOWING PROPOSED |
| | INSTALLATION LOCATION OF CONDENSING UNIT. |
| | |
| | 6. PAGE M2 NOTE CALLS FOR HVAC-1 CONDENSATE TO |
| | DISCHARGE INTO HUB DRAIN. CONDENSATE SHALL NOT |
| | DISCHARGE INTO SANITARY SYSTEM PER CITY ORDINANCE. |
| | CONDENSATE SHALL BE DISCHARGED IN AN APPROVED LOCATION |
| | IN ACCORDANCE WITH FBC-M 307.2.1. |
| | |
| | 7. PLANS SHOW EXHAUST DUCTS WITHIN THE RETURN AIR |
| | PLENUM SPACE. EXHAUST DUCTS UNDER POSITIVE PRESSURE |
| | SHALL NOT PASS THROUGH A PLENUM IN ACCORDANCE WITH |
| | FBC-M 601.5. |
| | |
| | 8. PLANS SHALL BE PROPERLY SIGNED AND SEALED WITH |
| | ORIGINAL SIGNATURE IN ACCORDANCE WITH FS 481. FULL |
| | TITLE BLOCK INFORMATION AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER ARE ALSO REQUIRED. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME: |
| | RONALD J REGUEIRO |
| | 561.805.6719 |
| | [email protected] |