| Plan Review Notes For Permit 09120451 |
| Permit Number |
09120451 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-11 15:45:48 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 3. SHOW THE LOCATION OF THE PORTABLE 2A:10BC RATED FIRE | | | EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS | | | AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 5. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL | | | HAVE NOT LESS THAN A 20-MINUTE FIRE PROTECTION RATING. | | | | | | 6. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE | | | SELF CLOSING AND SELF LATCHING. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE THE COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE THE COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|