| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET 1 OF 4, UNLESS OTHERWISE |
| | NOTED. ALL CODE ARTICLES REFERENCED ARE 2008 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} THE LOAD CALCULATION INDICATES A 400 AMP SERVICE |
| | WITH 1/0 CONDUCTORS, THE RISER DIAGRAM INDICATES 350 |
| | MCM (AND A 3/0???) BOTH OF WHICH DO NOT COMPLY WITH |
| | 310.15 (B)(6) FOR CONDUCTOR SIZE. 400 MCM WOULD BE |
| | CORRECT FOR A 400 AMP SERVICE, AND NO GROUND WIRE IN |
| | THE RISER.ALSO SEE 250.94 FOR INTERSYSTEM BONDING. |
| | |
| | THE ELECTRICAL NOTE REGTARDING ARC FAULT BREAKERS IN |
| | THE BEDROOMS IS INCORRECCT, SEE 210.12 2008 NEC. |
| | |
| | 3} THE PANEL LOCATION IN UNIT #3 IS IN VIOLATION OF |
| | 240.24 (D), CLOTHES CLOSET. |
| | |
| | 4} UNIT #1NEEDS A RECEPTACLE ADDED TO THE KITCHEN |
| | COUNTERTOP TO COMPLY WITH210.52 (C)(1) SPACING. SEE |
| | REVIEWED PLAN. |
| | |
| | 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH |
| | 250.66. SEE NOTE #1 REGARDING THE SUM OF THE SERVICE |
| | ENTRANCE CONDUCTORS. |
| | |
| | 6} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| | FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/805-6676 |
| | |