| Date |
Text |
| 2009-12-29 16:37:26 | 2007 FBC W/2009 REVISIONS |
| | LEVEL 3 ALTERATION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PLANS ARE REQUIRED TO BE PREPARED, SIGNED, |
| | SEALED AND DATED BY A FLORIDA LICENSED ARCHITECT OR |
| | ENGINEER. FS 481.229 AND FS 471.003 |
| | |
| | 2) PER 405.1, THE WORK AREA EXCEEDS 50 PERCENT OF THE |
| | AGGREGATE AREA OF THE BUILDING, WHICH MAKES THIS A |
| | LEVEL 3 ALTERATION. PLEASE CORRECT. |
| | |
| | 3) IF THIS IS A 3-UNIT APARTMENT BUILDING, THE |
| | OCCUPANCY TYPE IS R-2. PLEASE CORRECT. SEE FBC 310.1 |
| | |
| | 4) THE ENERGY CALCULATION FORM NEEDS TO BE SIGNED BY |
| | THE OWNER AS WELL AS THE PREPARER. FBC 13-103.1.1.2.2 |
| | REQUIRES THE FORM PREPARATION FOR MULTI-FAMILY |
| | DWELLINGS TO BE SIGNED AND SEALED BY AN ARCHITECT OR |
| | ENGINEER REGISTERED IN THE STATE OF FLORIDA. |
| | |
| | 5) PLEASE NOTE ON THE PLANS THAT THE EXISTING TENANT |
| | SEPARATION WALLS, AS WELL AS, THE FLOOR/CEILING |
| | SEPARATING TENANT SPACES ARE REQUIRED TO HAVE A ONE |
| | HOUR FIRE RATING PER FBC 708.1 AND FBC 711.3. THE |
| | BATHROOM LOCATED UNDER THE STAIRS IS REQUIRED TO HAVE |
| | ONE HOUR FIRE SEPARATION FROM THE STAIRS LEADING TO THE |
| | UNIT ABOVE. |
| | |
| | 6) SPECIFY THE WIND DESIGN INFORMATION INCLUDING WIND |
| | SPEED, EXPOSURE CATEGORY, ETC. ON THE PLANS. SEE FBC |
| | 1603.1.4. |
| | |
| | 7) SPECIFY THE REQUIRED COMPONENT AND CLADDING |
| | PRESSURES FOR THE WINDOW AND DOOR OPENINGS ON THE |
| | PLANS. SEE FBC 1604.9. THE ONES SPECIFIED ON THE PLANS |
| | ARE NOT CORRECT. |
| | |
| | 8) PROVIDE THE UL LISTING OR FILE NUMBER FROM AN |
| | APPROVED TESTING AGENCY FOR THE 1 HOUR FIRE RATED WALL |
| | SYSTEM THAT WILL BE INSTALLED. SEE FBC 703. |
| | |
| | 9) PLEASE CLARIFY WHICH WINDOWS ARE TO BE REPLACED AND |
| | WHICH OF THE EXISTING ONES WILL REMAIN. PLEASE NOTE |
| | THAT A 37 X 50 WINDOW DOES NOT MEET EGRESS SIZE |
| | REQUIREMENTS. SEE FBC 1026. |
| | |
| | 10) SUBMIT PRODUCT APPROVALS FOR THE HORIZONTAL SLIDING |
| | WINDOWS PER FAC RULE 9B-72, IF THEY ARE TO BE REPLACED. |
| | |
| | 11) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. FBC 106.3.3 CITY AMENDMENTS. |
| | |
| | 12) THE ROOM HOUSING THE DRYER FOR UNIT # 2 THAT |
| | LOCATED UNDER THE EGRESS STAIRS FOR UNIT #3 IS REQUIRED |
| | TO HAVE 1 ONE FIRE RATED WALLS AND CEILING THAT |
| | SEPARATE IT FROM THE STAIRS AND LANDING OF THE ADJACENT |
| | TENANT SPACE. FBC 708 AND 711. |
| | |
| | 13) SPECIFY DRAFTSTOPPING IN THE COMBUSTIBLE FLOOR |
| | CONSTRUCTION ABOVE AND IN LINE WITH THE DWELLING UNIT |
| | SEPARATIONS ON THE PLANS. SEE FBC 717.3. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |