Plan Review Notes
Plan Review Notes For Permit 09120440
Permit Number 09120440
Review Stop Z
Sequence Number 1
Notes
Date Text
2010-01-07 18:07:29FAILED
  
 PLEASE RESPOND TO COMMENTS IN WRITING. PLEASE NOTE THAT
 ADDITIONAL COMMENTS MAY ARISE BASED ON THE RESUBMITTED
 PLANS.
  
 1) STAFF VISITED THE SITE AND NOTED THAT THE PLANS
 SUBMITTED DO NOT MATCH ACTUAL SITE CONDITIONS:
  
 A. THERE IS AN EXISTING FIRE HYDRANT, STAND PIPE, AND
 TWO UNDERGROUND ACCESS COVERS THAT ARE NOT SHOWN WEST
 OF THE PROPOSED FUEL TANK ENCLOSURE.
 B. THE PARKING AREA SOUTH OF THE PROPOSED FUEL TANK
 ENCLOSURE HAS FIVE PARKING SPACES, NOT THREE AS SHOWN.
 C. THE TREE, INCLUDING SPECIES, IN THE TERMINAL ISLAND
 SOUTHWEST OF THE PROPOSED FUEL TANK ENCLOSURE IS NOT
 SHOWN.
  
 2) DUE TO THE DISCREPANCIES IN THE SUBMITTED PLAN AND
 ACTUAL SITE CONDITIONS, A SURVEY OF THE AREA OF WORK IS
 REQUIRED. THE PLANS SHALL MATCH THE SURVEY.
  
 3) THE FIRE HYDRANT REQUIRES A CLEAR AREA OF FOUR FEET
 TO THE REAR. ROUGH FIELD MEASUREMENTS INDICATE THAT THE
 HEDGE AND POSSIBLY THE ENCLOSURE WILL ENCROACH INTO THE
 CLEAR AREA.
  
 4) THE PODOCARPUS HEDGE SHALL BE INSTALLED AT FOUR FEET
 IN HEIGHT AND TWO AND A HALF FEET ON CENTER. THE PLANS
 SHALL BE REVISED TO STATE THIS.
  
 5) THE HEDGE SHALL BE SHOWN ON THE SITE PLAN.
  
 6) THE SITE PLAN SHALL INDICATE WHERE THE GATE TO THE
 ENCLOSURE IS LOCATED.
  
 7) PERMITS 09120440 (TANK), 09120442 (FENCE) AND
 09120443 (LANDSCAPE) SHALL ALL BE CONSISTENT PRIOR TO
 ZONING APPROVAL.
  
 8) THE MINOR PLANNED DEVELOPMENT AMENDMENT PLANS NEED
 TO BE REVISED TO REFLECT THE COMMENTS ABOVE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.