Plan Review Notes
Plan Review Notes For Permit 09120427
Permit Number 09120427
Review Stop P
Sequence Number 1
Notes
Date Text
2010-01-06 16:04:40DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 FUEL GAS
 FBC-2007 BUILDING
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH THE ARCHITECTURAL TITLE BLOCK. THE
 BUSINESS NUMBER (CERTIFICATE OF AUTHORIZATION) IS
 REQUIRED IN THE TITLE BLOCK. FAC 61G1-16.004(2) & FS
 481.2055.
  
 2. ALL SHEETS SIGNED, SEALED BY THE ARCHITECT OF RECORD
 SHALL BE SEALED BY AN IMPRESSION TYPE SEAL PER FAC
 61G1-16.00(1)(2) & FS 481.2055. ALSO THE DATE THE SEAL
 AND SIGNATURE ARE AFFIXED SHALL BE INDICATED UNDER THE
 SIGNATURE.
  
 2. ALL SHEETS WITH THE ENGINEERING TITLE BLOCK. THE
 CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. FAC 61G15-23.002(2) & FA 471.025.
  
 3. THE TITLE BLOCK OF EACH SHEET AND THE APPLICATION
 SHALL INCLUDE THE SUITE NUMBER OF THE PROJECT. SECTION
 106.1.1.
  
 4. SHT A-1A ROOM 107 LOUNGE SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE (GARBAGE DISPOSAL NOT ALLOW
 IN CLEARANCE AREA)
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (CABINET DOORS NOT
 APPROVED)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.5 CLEARANCES AND CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED)
  
 6. SHT A-4 FINISH SCHEDULE INDICATES PAINT OVER WR GYP
 BOARD. SECTION 1210.2 REQUIRES THE SURFACE WITHIN 2
 FEET OF A WATER CLOSET UP TO 4 FEET ABOVE THE FLOOR TO
 BE SMOOTH, HARD & NONABSORBENT. A PAINTED WALL BOARD
 DOES NOT MEET THE "HARD" REQUIREMENT. PLEASE SHOW
 COMPLIANCE.
  
 7. SHT P-3 AN ISOMETRIC WATER RISER DIAGRAM IS REQUIRED
 FOR THE R.O. PIPING. SECTION 106.3.5.1.3. SHOW ALL PIPE
 SIZING, VALVES ETC.
  
 8. SHTS P-3 KEY NOTE #2 AND P-6 R.O. ROOM PIPING
 INDICATE SCHEDULE 80 PVC FOR THE R.O. PIPING. PER TABLE
 605.4 PVC IS NOT APPROVED FOR DISTRIBUTION PIPING.
  
 9. SHTS P-2 FLOOR PLAN & P-4 SANITARY RISER DIAGRAM
 INDICATE DRY HORIZONTAL VENT PAST THE FLOOR SINK IN
 BICARB ROOM 108. SECTIONS 905.3 & 905.4.
  
 10. SHT P-5 DETAIL 2 INDICATES A GAS WATER HEATER. A
 SEPARATE GAS PERMIT AND ARE REQUIRED. SEE GAS REVIEW
 FOR REQUIREMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  